| Plan Review Notes For Permit 20060338 |
| Permit Number |
20060338 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-07-10 12:44:40 | PLAN REVIEW - FUEL GAS GENERATOR | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | | | | 1) GAS ISOMETRIC DRAWING: | | | A) THE DRAWING IS INCOMPLETE AND MUST BE MODIFIED TO | | | SHOW THE ENTIRE SYSTEM INCLUDING ALL BRANCH PIPES FROM | | | THE METER TO THE MOST REMOTE OUTLET. THE BTUH LOAD OF | | | EACH APPLIANCE AND THE LOCATIONS OF REGULATORS SHALL BE | | | INDICATED ON THE DRAWING- SECTIONS G2412.3 & G2412.4 | | | FBC RES. | | | B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM | | | FROM THE METER TO THE MOST REMOTE OUTLET, AND BRANCH | | | LENGTH SIZES- SECTIONS G2413.4.1, G2413.4.2 & | | | G2413.4.3. | | | B) PROVIDE DELIVERY PRESSURE TO THE GENERATOR FROM THE | | | OUTLET OF THE REGULATOR- SECTION G2421.1 | | | C) CORRECT THE BTUH LOAD OF THE GENERATOR. THE | | | SUBMITTED SPECS INDICATE 306,000 BTUH FULL LOAD- | | | G2413.2 FBC RES. | | | | | | |
|