| Plan Review Notes For Permit 20060323 |
| Permit Number |
20060323 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-07-10 11:31:31 | GENERATOR PAD | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) NEED SIGNED AND SEALED PAD AND GENERATOR TIEDOWN | | | DRAWINGS FROM AN ARCHITECT OR ENGINEER FBC R301.1.3 | | | (DRAWINGS PROVIDED ARE DESIGNED BASED ON AN OLDER CODE) | | | 2) PLEASE SHOW THE CODE USED AND THE WIND DESIGN | | | CRITERIA ON THE (PAD AND GENERATOR TIEDOWN) DRAWING FBC | | | R301.2.1 | | | |
|