| Plan Review Notes For Permit 20060308 |
| Permit Number |
20060308 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-06-15 14:37:58 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE INFORMATION ON THE SITE SPECIFIC ENGINEERING | | | DOES NOT CORRESPOND WITH THE WINDOW AND DOOR SCHEDULE. | | | THE 4 DOORS ARE INCORRECTLY LISTED AS WINDOWS WITH THE | | | WRONG PRODUCT APPROVAL NUMBERS AND DESIGN PRESSURES ON | | | THE SITE SPECIFIC ENGINEERING. PLEASE CORRECT ENTRY | | | DOOR #16 AND SLIDING GLASS DOORS #8, #11A AND #13. THE | | | MAXIMUM DESIGN PRESSURES ARE +/- 50 PSF FOR THE ENTRY | | | DOOR AND +/- 60 PSF FOR THE SLIDING GLASS DOORS. FBC | | | 107 |
|