| Plan Review Notes For Permit 20060289 |
| Permit Number |
20060289 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-07-10 08:12:56 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT | | | CURRENT AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. | | | NEC 110.10 | | | | | | 2) PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE | | | MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT | | | AVAILABLE PER NEC 110.24. |
|