| Plan Review Notes For Permit 20060233 |
| Permit Number |
20060233 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-07-06 08:50:11 | PLUMBING 2ND REVIEW COMMENTS: 20060233 | | | 1) PLAN SHALL BE DIGITALLY SIGNED AND SEALED PER | | | FLORIDA ADMIN CODE | | | 2) PLAN ONLY SHOWS MAIN LOOP. PLEASE INCLUDE ZONE | | | VALVES AND BRANCH LINES. COMPLETE IRRIGATION SYSTEM | | | MUST BE DRAWN ON PLANS. FBC 107.2.1 | | | 3) ADD NOTE PIPING FROM THE WATER METER UP TO AND | | | INCLUDING THE RPZ BACKFLOW DEVICE MUST BE MIN TYPE L | | | COPPER, PERMITTED, AND INSTALLED ONLY BY LICENSED | | | PLUMBING CONTRACTOR. PER 2017 W.P.B CROSS CONNECTION | | | MANUAL AND F.S 489 | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | (CAP GOVERNMENT) | | | [email protected] | | | | | | |
|