| 2020-08-26 17:38:18 | 8/26/2020 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | 1. A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL |
| | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT |
| | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE |
| | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. |
| | PROVIDE COMPLETE PLANS AND GAS RISER THAT REFLECTS THE |
| | ENTIRE SCOPE OF GAS WORK TO BE DONE. AT THIS TIME. WPB |
| | AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | 2. SUBMIT THE TABLE FOR INSTALLATION CLEARANCES FROM |
| | THE TANKLESS WATER HEATER INSTALLATION MANUAL. THE |
| | MANUAL REQUIRES A CLEARANCE OF EITHER 4 FEET OR 12 |
| | INCHES FROM ANY OPERABLE WINDOWS OR DOORS. SHOW THE |
| | LOCATION OF ALL OPERABLE WINDOWS AND DOORS ON THE PLAN |
| | AND THE DISTANCE OF THE TANKLESS WATER HEATER FROM |
| | EACH. WPB AMENDMENTS TO THE FBC SEC. 107.2.1. |
| | |
| | 3. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC |
| | FUEL GAS RES. SEC. G2421.1. |
| | |
| | 4. SUBMIT MANUFACTURES SPECIFICATIONS FOR THE TANKLESS |
| | WATER HEATER. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| | |
| | 5. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL |
| | GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC FUEL GAS RES |
| | SECS. G2413.4.1, G2413.4.2. |
| | |
| | ATELYO BELISLE |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6695 |
| | |