Plan Review Notes
Plan Review Notes For Permit 20060205
Permit Number 20060205
Review Stop E
Sequence Number 1
Notes
Date Text
2020-07-22 21:53:19ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SERVICE RISER DIAGRAM DOESN'T MATCH SERVICE SHOWN ON
 PLANS. SERVICE RISER DIAGRAM IS A CODE COMPLIANT
 INSTALLATION BUT SERVICE SHOWN ON PLAN SAYS "NEW METER"
 SHOWS NO GUTTER AND ONLY ONE SERVICE DISCONNECTING
 MEANS. SERVICE DISCONNECTS MUST BE GROUPED PER NEC
 230.72A
  
 2. NOTE ON PLANS STATES "SMOKE ALARMS ARE REQUIRED
 OUTSIDE OF SLEEPING AREA" PLEASE CHANGE TO SAY "INSIDE
 AND IMMEDIATLY OUTSIDE" PER FBC RE 314 &315
  
 3. SHOW SMOKE/CARBON ALARM LOCATIONS ON PLAN PER FBC RE
 314 & 315.
  
 4.NO RECEPTACLE SHOWN FOR GAS TANKLESS WATER HEATER??
 FBC 107.2.1
  
 5. SWITCH CONTROLLED LIGHT REQUIRED AT ATTIC ACCESS NEC
 210.70A3
  
 6. RECEPTACLE REQUIRED ON 2ND FL BALCONY NEC210.52E3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  