| 2020-07-31 10:58:23 | 07/31/20 2ND GAS/ REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THIS DRAWING IS A DUPLICATE OF ANOTHER DRAWING FOR A |
| | DIFFERENT REVIEW AND IT IS INCOMPLETE, IT MUST BE |
| | MODIFIED TO SHOW THE ENTIRE SYSTEM INCLUDING ALL BRANCH |
| | PIPES FROM THE METER TO THE MOST REMOTE OUTLET, YOU MAY |
| | WANT TO REDRAW IT. THE SIZE OF THE RECORDED SYSTEM IS 1 |
| | 1/2" AND YOU HAVE 1" BRANCHING OUT SO PLEASE CORRECT ON |
| | NEW DRAWING. SHOW THE BTU'S LOAD OF EACH APPLIANCE AND |
| | THE LOCATIONS OF REGULATORS SHALL BE INDICATED ON THE |
| | DRAWING- SECTIONS G2412.3 & G2412.4 FBC RES. LIST THE |
| | BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON |
| | THE SYSTEM. REFER TO THE 2017 FBC RES. SEC. G2413. |
| | |
| | 2. PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM |
| | FROM THE METER TO THE MOST REMOTE OUTLET, AND BRANCH |
| | LENGTH SIZES- SECTIONS G2413.4.1, G2413.4.2 & |
| | G2413.4.3. |
| | |
| | 3. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| | PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 5. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2017 FBC RES. SEC. G2413.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |