| Plan Review Notes For Permit 20060131 |
| Permit Number |
20060131 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-07-02 08:02:21 | WINDOWS/DOORS/SHUTTERS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW ON THE FLOOR PLAN THE WINDOW, DOOR AND | | | SHUTTER LOCATIONS (WHAT GOES WHERE) AND SIZES (WIDTH | | | AND HEIGHT). | | | 2) PLEASE SHOW THE DISTANCE FROM THE CORNER OF THE | | | BUILDING TO THE EDGE OF THE WINDOWS TO DETERMINE IF IN | | | WIND ZONE 4 OR 5. | | | 3) FBC R 301, COMPLETE THE FORM PROVIDED AT THE FRONT | | | COUNTER "SCHEDULE FOR INSTALLATION OF OPENING | | | PROTECTIVE DEVICES OR ASSEMBLIES" OR PROVIDE ALL | | | INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL | | | SPREADSHEET). WHEN COMPLETING THE INSTALLATION | | | SCHEDULE, PLEASE NOTE FACTORS APPLY DEPENDING ON | | | SUBSTRATE, EDGE DISTANCE AND FASTENER. FOR FASTENER, IF | | | USING TAPCON, BE SPECIFIC AS TO WHICH TAPCON (TAPCON | | | W/ADVANCED THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR). | | | FORMS CAN BE PROVIDED BY EMAILING AND ASKING FOR | | | "SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE | | | DEVICES OR ASSEMBLIES" AT [email protected] |
|