| Plan Review Notes For Permit 20060048 |
| Permit Number |
20060048 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-06-04 09:58:51 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS AN INDICATION OF AN EXISTING FIRE HYDRANT | | | ALONG TANGLEWOOD CT THAT WILL BE BLOCKED BY THE NEW | | | PROPOSED LOCATION OF THE FENCE LINE. | | | | | | THIS FIRE HYDRANT NEEDS TO BE ACCESSIBLE FOR FIRE | | | DEPARTMENT USE AT ALL TIMES. | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | | | | 2) KNOX PADLOCKS ARE RECOMMENDED- NOT REQUIRED- FOR | | | 24HR FD ACCESS. SHOULD A KNOX PADLOCK NOT BE PROVIDED | | | THE GATE CHAIN/LOCK MAY BE CUT AND LEFT UNSECURED WHERE | | | A KNOX PADLOCK COULD BE RESECURED. | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|