| Date |
Text |
| 2020-06-15 13:47:04 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20060036 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE GREASE DUCT DRAWINGS FOR THIS |
| | PROJECT; INCLUDE LENGTH, SLOPE, CLEANOUTS, TERMINATION |
| | LOCATIONS THAT MEET EXHAUST CLEARANCES. ALSO SHOW |
| | DETAIL DRAWINGS OF CONNECTION TO THE HOOD AND THE |
| | TERMINATION AT ROOF. FBC FS 107.2.1 |
| | |
| | 2) PLEASE PROVIDE A FLOOR PLAN LAYOUT SHOWING THE HOOD |
| | AND MAKE UP AIR LOCATIONS AND APPLIANCES UNDER THE |
| | HOOD. FBC FS 107.2.1 |
| | |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |