2020-06-10 13:50:121. NO ADDRESS PROVIDED IN THE PLAN TITLE BLOCK
 INFORMATION.
 2. PDF 5 GIVES SPECIFICATIONS OF HOOD SUPPRESSION
 SYSTEM TO BE INSTALLED, IF NOT BY OTHERS:
 A. PROVIDE MANUFACTURER SPECIFICATION SHEETS FOR ALL
 COMPONENTS (I.E. NOZZLES, FUSIBLE LINKS, CANISTERS,
 ETC.)
 B. PLEASE PROVIDE LAYOUT OF HOOD SYSTEM WITH APPLICABLE
 APPLIANCE DETAIL TO BE INSTALLED.
 3. PER FBC 904.11.1, A MANUAL ACTIVATION DEVICE SHALL
 BE LOCATED ALONG THE EGRESS PATH AND BE A MINIMUM OF 10
 FEET AND A MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST
 SYSTEM. THE DEVICE SHALL BE MOUNTED 42-48 INCHES ABOVE
 THE FLOOR AND SHALL CLEARLY IDENTIFY THE HAZARD
 PROTECTED.
 4. DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE
 SURFACE.
 5.ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY
 WITH NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  