Plan Review Notes
Plan Review Notes For Permit 20060031
Permit Number 20060031
Review Stop P
Sequence Number 3
Notes
Date Text
2020-09-25 10:25:083RD REVIEW FBC-2017 RES. PLUMBING
 PERMIT- 20060031
 9/25/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 AS PREVIOUSLY NOTED IN THE FUEL GAS REVIEW OF THE
 PROJECT ON 7/16/20 THE GAS PIPING AND THE GENERATOR
 INSTALLATIONS SHALL BE UNDER SEPARATE PERMIT. PLEASE
 PLACE A LARGE BOLD NOTE ON THE PLANS FOR CLARIFICATION.
 A REVIEW OF THE GAS PLANS AND GENERATOR WILL NOT BE
 PERFORMED AT THIS TIME- SECTION 107.1 WPB.
  
 1) THE MISSING PLAN SHEET PS1.1 HAS BEEN PROVIDED WHICH
 IS MORE GAS PIPING AND GENERATOR INFORMATION, HOWEVER A
 WATER RISER FOR THE PROJECT HAS NOT BEEN PROVIDED. NEW
 PLAN SHEETS INDICATE AN EXTERIOR GAS-FIRED TANKLESS
 WATER HEATER HAS BEEN ADDED. SHEET P1.1: PLEASE PROVIDE
 A WATER RISER AND A FLAT LINE DRAWING SHOWING THE HOT
 AND COLD WATER SUPPLY RUNS FROM THE NEW WATER HEATER
 LOCATION TO THE NEW AND RELOCATED PLUMBING FIXTURES AND
 APPLIANCES- SECTION P2903 FBC RES & SECTION 107.2.1
 WPB.
  
 1A) SHOW LOCATIONS WHERE PIPING WILL BE RUN UNDERSLAB.
 INDICATE THE TYPE OF PIPING AND HOW IT WILL BE
 PROTECTED FROM CORROSION- SECTION P2603.3 FBC RES.
  
 1B) PLEASE SHOW THE LOCATIONS OF ALL REQUIRED WATER
 HAMMER ARRESTORS AND BACKFLOW PREVENTERS- SECTIONS
 P2902.3 & P2903.5 FBC RES.
  
 1C) LIST THE MAKE AND MODEL OF THE NEW WATER HEATER ON
 THE PLAN AND SUBMIT MANUFACTURER'S SPECIFICATIONS. THE
 SPECS SUBMITTED SHALL INCLUDE THE EFFICIENCY RATING,
 AND A TEMPERATURE RISE CHART FOR SIZING THE REQUIRED
 GPM FLOW TO THE FIXTURES- SECTIONS G2448.1, P2903.1 FBC
 RES. AND TABLE C404.2 FBC EC.
  
 1D) INDICATE THE HOT WATER PIPES WILL INSULATED WITH
 R-3 PIPE INSULATION- SECTION R403.5.3 FBC RES.
  
 2) SHEETS A-001, P1.1: SHOW SLAB CUT LOCATIONS FOR NEW
 UNDERSLAB DRAIN PIPING INSTALLATIONS AND PROVIDE A SLAB
 REPAIR DETAIL- SECTION 107.21 WPB AND SECTION R318.1.3
 FBC RES. PLEASE NOTE THE HORIZONTAL DISTANCE FROM THE
 CENTERLINE OF THE NEW SHOWER DRAIN OUTLET TO THE
 CENTERLINE OF THE INLET OF THE EXISTING TRAP SHALL NOT
 EXCEED 30 IN- SECTION P3201.6 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  