| 2020-07-18 15:09:59 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20060031 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE ENERGY CALCULATIONS GAUGE AND MANUAL |
| | J. FBC EC 101.5.1.1.2 |
| | |
| | 2) PROVIDE VENTILATION CALCULATIONS FOR THIS NEW SF |
| | OCCUPANCY. FBC M 401.2 |
| | |
| | 3) PROVIDE MANUAL J CALCULATIONS FOR THE MECHANICAL |
| | SYSTEM. FBC EC R 403.7 |
| | |
| | 4) PROVIDE INFORMATION ON THE OUTDOOR CONDENSER |
| | ANCHORAGE. FBC RES M1307.2 |
| | |
| | 5) PROVIDE MECHANICAL SHEETS SHOWING THE MECHANICAL |
| | SYSTEM INCLUDING ALL EQUIPMENT AND DUCT WORK. FBC FS |
| | 107.2.1 |
| | |
| | 6) PROVIDE ON THE DRAWING, HOW THE MECHANICAL SYSTEM |
| | WILL HAVE A BALANCED RETURN AIR SYSTEM. FBC RES M1602.3 |
| | |
| | 7) PLEASE PROVIDE SPEC SHEET SON THE KITCHEN RANGE AND |
| | ASSOCIATED HOOD. FBC FS 107.2.1 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |