2020-06-17 10:01:132017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20060031
 ADD: 314 FLAMINGO DRIVE
 CONT: CASA BUENA CONSTRUCTION/ PEDRO FURTADO
 TEL: 818-620-7860
 E-MAIL: DAMONMONTYDMAC.COM
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 17/2020
 ACTION: DENIED
  
 1A) THERE IS STILL A OPEN PERMIT 19080808 FROM THE SAME
 CONTRACTOR FOR A LIVE/ WORK LOFT UNIT.
 1B) WHEN YOU PUT THE ADDRESS IN 314 FLAMINGO DRIVE INTO
 THE INTERNET THE RESULTS ARE FOR JAMES SWOPE FINE ARTS
 CONSERVATION WITH OFFICE HOURS AND WHAT APPEARS
 POSSIBLY VIEWINGS, CLASSES AND OR AUCTIONS SINCE THERE
 IS ALSO TICKET SALES. WE WILL NEED A LETTER FROM THE
 OWNER WHAT THE END INTENT FOR THIS BUILDING.
 1C) THE SHEET 002A INDICATES A LEVEL 2 ALTERATION TO A
 SINGLE FAMILY HOUSE. THE PALM BCH COUNTY HAS THE LAST
 KNOWN USE AS A WAREHOUSE. THIS WOULD BE CONSIDERED A
 CHANGE IN OCCUPANCY AND THE PLANS DEVELOPED UNDER THE
 2017 FBC-EXISTING BUILDING AND THE 2017 RESIDENTIAL
 CODE IF THE USE IS TO BE STRICTLY USED FOR A SINGLE
 FAMILY DWELLING.
 1D) SHEET A1.01 MISSING INFORMATION. 2017 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATIVE CODE, 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 UNDER WHICH BUILDING CODE WERE THE PLANS DEVELOPED
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED IN CHAPTER 3 & 4 FBC-B
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED, NO
 SQ. FOOTAGE OF OCCUPANCIES ON PLANS,
 RATING OF FIRE BARRIER ASSEMBLIES, VERTICAL AND
 HORIZONTAL
 BUILDING FIRE SPRINKLERED OR NOT, FIRE SPRINKLER PLANS
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 SITE REQUIREMENTS/ ACCESSIBLE ROUTE
 TOILET AND BATHING FACILITIES/ KITCHENETTE
 DRINKING FOUNTAINS
 2) THE DESIGNER OF RECORD HAS NOT DISCLOSED UNDER WHAT
 BUILDING CODE THESE PLANS WERE DEVELOPED. STATEWIDE THE
 2017 FAMILY OF FLORIDA BUILDING CODES WERE ADOPTED ON
 DEC. 31/ 2017. UPDATE PLANS.
  
 3) THE DESIGNER OF RECORD HAS NOT DISCLOSED UNDER THE
 2017 FLORIDA EXISTING BUILDING CODE WHAT METHOD THE
 PLANS WERE DEVELOPED. FOR THIS REVIEW THE REVIEWER WILL
 BE USING BOTH THE 2017 FBC-B AND THE 2017 EXIST.
 BUILDING CODE CHAPTER 10 CHANGE OF OCCUPANCY SECTION
 1001.2.2. CHANGE OF OCCUPANCY CLASSIFICATION OR GROUP.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 1002 THROUGH 1012
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION AND A CHANGE TO ANOTHER GROUP WITHIN AN
 OCCUPANCY CLASSIFICATION.
  
 THIS BUILDING WE COULD NOT FIND A BUSINESS TAX RECEIPT
 / BUT PALM BEACH COUNTY PROPERTY APPRAISERS HAS THE
 OCCUPANCY TYPE LISTED AS WAREHOUSE/ STORAGE. THAT IS
 WHY WE ARE LISTING THIS REVIEW AS A CHANGE IN
 OCCUPANCY/ CHANGE IN USE.
  
 4A) PLEASE SHOW COMPLIANCE WITH THE 2017 EXIST. BUILD.
 CODE SECTION 1002.1 COMPLIANCE WITH THE BUILDING CODE.
 WHERE THE CHARACTER OR USE OF AN EXISTING BUILDING OR
 PART OF AN EXISTING BUILDING IS CHANGED TO ONE OF THE
 FOLLOWING SPECIAL USE OR OCCUPANCY CATEGORIES AS
 DEFINED IN THE FLORIDA BUILDING CODE, BUILDING, THE
 BUILDING SHALL COMPLY WITH ALL OF THE APPLICABLE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING:
 406.3.MOTOR VEHICLE-RELATED OCCUPANCIES.
 EXIST BLDG. CODE 406.4.6 MIXED OCCUPANCY SEPARATION.
 PARKING GARAGES SHALL BE SEPARATED FROM OTHER
 OCCUPANCIES IN ACCORDANCE WITH SECTION 508.1 OF THE
 FBC-B. WHERE A BUILDING CONTAINS MORE THAN ONE
 OCCUPANCY GROUP, THE BUILDING OR PORTION THEREOF SHALL
 COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION 508.2,
 508.3 OR 508.4, OR A COMBINATION OF THESE SECTIONS.
 PLEASE NOTE PARKING GARAGES ARE PART OF THE SPECIALTY
 OCCUPANCIES FOUND IN CHAPTER 4 AND WILL REQUIRE FIRE
 SEPARATION AS PER TABLE 508.4 OF THE FBC-B. PLEASE ALSO
 NOTE FOOTNOTE B. THE REQUIRED SEPARATION FROM AREAS
 USED ONLY FOR PRIVATE OR PLEASURE VEHICLES SHALL BE
 REDUCED BY 1 HOUR BUT NOT LESS THAN 1 HOUR. OPENING
 PROTECTIVES FOR DOORS CAN BE FOUND UNDER THE FBC-B
 TABLE 716.5. PRIVATE GARAGES UNDER 1,000 SQ. IS TO BE
 CONSIDERED AN U OCCUPANCY (UTILITY). IN THE 2017 FBC-B
 406.3.1 THE CLASSIFICATION FOR A PRIVATE GARAGE AS
 UTILITY STILL REQUIRES A 1 HOUR FIRE BARRIER IN
 COMPLIANCE WITH SECTION 707 OF THE FBC-B.
  
 4B) PLEASE NOTE THAT PRIVATE GARAGES NEED ONLY TO
 COMPLY WITH 406.3.1 THROUGH 406.3.6. VENTILATION
 REQUIREMENTS FOUND UNDER 406.6.2 ARE NOT REQUIRED!
  
 5A) THE IDEA OF CALLING THIS STRUCTURE A LIVE/ WORK
 UNIT DOES NOT MEET THE CRITERIA FOUND IN SECTION
 419.1.1 LIMITATIONS OF THE 2017 FBC-B. THE
 NON-RESIDENTIAL AREA IS PERMITTED TO BE NOT GREATER
 THAN50 % OF THE AREA OF EACH LIVE/ WORK UNITS.
  
 5B) THE OTHER OCCUPANCY SEPARATION THAT WILL NEED TO
 OCCUR IS THE RESIDENTIAL R-3 VERSES THE A-3 OCCUPANCY
 (GALLERY). TABLE 508.4 OF THE 2017 FBC-B WILL ALSO
 REQUIRE A 1 HOUR FIRE SEPARATION PER TABLE 508.4 FOR A
 SPRINKLERED BUILDING.
  
 6) SHEET A.1.1 SHOWS A NEW STOREFRONT DOORS AND GARAGE
 DOOR PLEASE PROVIDE COMPLIANCE WITH:
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,OVERHEAD GARAGE DOOR
 (B) WINDOWS AND MULLIONS (POSSIBLE SIDELIGHTS)
  
 7) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 8) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 10) SHEET S01 PROVIDES THE WIND DESIGN CRITERIA. BUT
 THE NEGATIVE PRESSURES ARE ABOUT 2.0 PSF LOW FOR
 EXPOSURE C. THE MEAN ROOF HEIGHT IS NOT GIVEN, NEGATIVE
 PRESSURES ARE TO BE TAKEN AT THE ROOF LINE. 2017 FBC-B
 1603.1.4 WIND DESIGN DATA. WIND EXPOSURE. APPLICABLE
 WIND DIRECTION IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED. TABLE 1609.7.2. HEIGHT AND EXPOSURE. TABLE
 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & EXPOSURE.
 PROVIDE THE MEAN ROOF HEIGHT FOR THE BUILDING. 1609.3.1
 WIND SPEED CONVERSION VULT TO VASD.
  
 11) PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  
 12) IMPACT FEES - DIGITAL SUBMITTALS: PLANS WILL BE
 REVIEWED BY THE PBC IMPACT FEE OFFICE DIGITALLY VIA
 PROJECT DOX UPON NOTIFICATION BY THIS OFFICE.
 NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST FINAL
 FORM. YOU MAY COORDINATE WITH THE IMPACT FEE OFFICE AT
 (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL IMPACT
 FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME THE
 FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM CAN
 BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRAT
 ION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
  
 13). A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717 / FAX: 561-805-6676
 E-MAIL: [email protected]
  
  