| 2020-06-10 14:16:11 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20060027 |
| | 6/10/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 1: PLEASE PROVIDE A SCOPE OF WORK FOR PLUMBING |
| | ON THE PLAN- SECTION 107.2.1 WPB. |
| | |
| | 2) SHEET 1: PLEASE CLARIFY IF THE EXISTING TUB AND |
| | SHOWER DRAIN OUTLETS WILL BE RELOCATED TO ACCOMMODATE |
| | THE NEW SHOWER INSTALLATIONS. IF RELOCATING THE DRAINS |
| | PLEASE NOTE THE FOLLOWING: |
| | A) REFER TO SECTION 1002.1 FBC P: THE HORIZONTAL |
| | DISTANCE FROM THE CENTERLINE OF THE NEW SHOWER DRAIN |
| | OUTLET TO THE CENTERLINE OF THE INLET OF THE EXISTING |
| | TRAPS SHALL NOT EXCEED 30?. PLEASE PLACE A NOTE ON THE |
| | PLAN INDICATING COMPLIANCE. |
| | B) RELOCATING THE SHOWER DRAIN OUTLETS WILL REQUIRE THE |
| | FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE REINFORCING |
| | STEEL OR POST STRESSED FLOOR TENDONS. PLEASE PLACE A |
| | NOTE ON THE PLANS TO VERIFY COMPLIANCE WILL BE MET- |
| | SECTION 107.2.1 WPB. |
| | C) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB |
| | WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE |
| | AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED |
| | FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION |
| | 714.4.1.2 FBC B. |
| | |
| | 3) SHEET 1: PROVIDE A SHOWER PAN DETAIL- SECTION |
| | 417.5.2 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |