| 2020-07-15 11:17:16 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20060009 2600 N MILITARY TRL |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. PER WPB FBC 107.2.1, PROVIDE PLAN COMPLYING WITH WPB |
| | FBC 107.2.1.3 (QUALITY OF PLANS) SIGNED AND STAMPED BY |
| | THE DESIGN PROFESSIONAL IN ACCORDANCE WITH WPB FBC |
| | 107.1 SHOWING THE FULL SCOPE OF THE WORK INCLUDING BUT |
| | NOT LIMITED TO THE FOLLOWING: |
| | |
| | A. FLOOR PLAN SHOWING ALL IMPACTED DORM ROOMS. INDICATE |
| | GROUND FLOOR AND/OR ELEVATED FLOOR. |
| | B. DIMENSIONS OF THE DORM, BATHROOMS AND SHOWER |
| | ENCLOSURES |
| | C. DETAIL FOR SHOWER PAN (INCLUDE TYPE OF MATERIAL), |
| | CURB AND DRAIN COMPLYING WITH SHOWING COMPLIANCE WITH |
| | FBC PL SECTION 417. |
| | E. SPECIFICATION FOR SHOWER VALVE SHOWING COMPLIANCE |
| | WITH FBC PL 424.3. WHERE A HAND HELD SHOWER IS |
| | REQUIRED, COMPLY WITH FBC PL 424.2 |
| | F. LOCATION OF EXISTING SERVICE SINK OR PROVIDE NEW |
| | SERVICE SINK TO SHOW COMPLIANCE WITH FBC PL TABLE 403.1 |
| | G. PROVIDE ALL CLEAR FLOOR SPACES AND TURNING SPACES |
| | FOR ACCESSIBLE PLUMBING FIXTURES IN ACCORDANCE WITH FBC |
| | ACC SECTIONS 304 AND 305 |
| | H. PROVIDE DETAILS FOR ACCESSIBLE FIXTURES SHOWING |
| | COMPLIANCE WITH FBC ACC CHAPTER 6. |
| | I. PER FBC ACC 806.2.4, PROVIDE AT LEAST ONE BATHROOM |
| | THAT IS PROVIDED AS PART OF A GUEST ROOM AND COMPLIES |
| | WITH 603. NO FEWER THAN ONE WATER CLOSET, ONE LAVATORY, |
| | AND ONE BATHTUB OR SHOWER SHALL COMPLY WITH APPLICABLE |
| | REQUIREMENTS OF 603 THROUGH 610. IN ADDITION, REQUIRED |
| | ROLL-IN SHOWER COMPARTMENTS SHALL COMPLY WITH 608.2.2 |
| | OR 608.2.3. TOILET AND BATHING FIXTURES REQUIRED TO |
| | COMPLY WITH 603 THROUGH 610 SHALL BE PERMITTED TO BE |
| | LOCATED IN MORE THAN ONE TOILET OR BATHING AREA, |
| | PROVIDED THAT TRAVEL BETWEEN FIXTURES DOES NOT REQUIRE |
| | TRAVEL BETWEEN OTHER PARTS OF THE GUEST ROOM. |
| | J. PER FBC ACC 806.2.4.1, IF VANITY COUNTER TOP SPACE |
| | IS PROVIDED IN NON-ACCESSIBLE GUEST TOILET OR BATHING |
| | ROOMS, COMPARABLE VANITY COUNTER TOP SPACE, IN TERMS OF |
| | SIZE AND PROXIMITY TO THE LAVATORY, SHALL ALSO BE |
| | PROVIDED IN ACCESSIBLE GUEST TOILET OR BATHING ROOMS. |
| | K. PER FBC ACC 806.4, PLEASE NOTE THIS SECTION DOES NOT |
| | RELIEVE THE OWNER OF THE RESPONSIBILITY OF PROVIDING |
| | ACCESSIBLE ROOMS IN CONFORMANCE WITH SECTION 224 AND |
| | 806 OF THIS CODE. IN ALL BUILDINGS, STRUCTURES AND |
| | FACILITIESLICENSED AS A HOTEL, MOTEL OR RESORT |
| | CONDOMINIUM PURSUANT TO CHAPTER 509, F.S., A NUMBER OF |
| | ROOMS EQUALING AT LEAST 5 PERCENT OF THE GUEST ROOMS |
| | MINUS THE TOTAL NUMBER OF REQUIRED (ACCESSIBLE) ROOMS |
| | REQUIRED BY TABLE 224.2 SHALL PROVIDE THE FOLLOWING |
| | ADDITIONAL SPECIAL ACCESSIBILITY FEATURES: |
| | (I) GRAB RAILS IN BATHROOMS AND TOILET ROOMS WHICH |
| | COMPLY WITH SECTION 604.5. |
| | (II) ALL BEDS IN DESIGNED ACCESSIBLE GUEST ROOMS SHALL |
| | BE OPEN-FRAME TYPE THAT ALLOWS THE PASSAGE OF LIFT |
| | DEVICES. |
| | (III) WATER CLOSETS THAT COMPLY WITH SECTION 604.4. |
| | |
| | 2A. PER WPB FBC 107.1,ALL PLANS TO BE SIGNED AND SEALED |
| | BY THE DESIGNER IN ACCORDANCE WITH FAC AND FS. DESIGNER |
| | TO PROVIDE DIGITAL SIGNATURE IN ACCORDANC WITH FAC AND |
| | FS OR SHALL PROVIDE SIGNED AND SEALED PAPER DOCUMENT |
| | PRIOR TO PERMIT ISSUANCE.CALL 561-805-6724 FOR |
| | ADDITIONAL INFORMATION |
| | 2B. SEE WPB FBC 107.3.4.3 CERTIFICATION BY CONTRACTOR. |
| | PLEASE NOTE THE EXCEPTION TO ENGINEERED PLANS UNDER |
| | 471.003(H) ELECTRICAL/ PLUMBING/ MECHANICAL, |
| | 481.229(1)(C) (BUILDING) REQUIRES THE CONTRACTOR FOR |
| | THAT TRADE THAT WILL BE LICENSED IN THAT TRADE, WILL |
| | ALSO BE THE CONTRACTOR THAT DESIGNS THE SYSTEM UNDER |
| | THAT TRADE. THE CONTRACTOR (QUALIFIER) THAT CREATED / |
| | DRAWN THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES |
| | AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME, |
| | SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE |
| | LICENSED IN AND PLANS DRAWN. FOR EACH TRADE THE |
| | CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER THE TRADE |
| | LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR NAME AND |
| | LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE DRAWN BY |
| | ONE INDIVIDUAL, THEY WOULD HAVE TO BE LICENSED AS A |
| | BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO SUBMIT |
| | ALL THESE TRADES UNDER ONE SHEET. |
| | |
| | A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| | THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| | RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS |
| | FROM THE FIRST REVIEW. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20060009 2600 N MILITARY TRL |
| | |