Plan Review Notes
Plan Review Notes For Permit 20060009
Permit Number 20060009
Review Stop P
Sequence Number 1
Notes
Date Text
2020-07-15 11:17:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20060009 2600 N MILITARY TRL
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. PER WPB FBC 107.2.1, PROVIDE PLAN COMPLYING WITH WPB
 FBC 107.2.1.3 (QUALITY OF PLANS) SIGNED AND STAMPED BY
 THE DESIGN PROFESSIONAL IN ACCORDANCE WITH WPB FBC
 107.1 SHOWING THE FULL SCOPE OF THE WORK INCLUDING BUT
 NOT LIMITED TO THE FOLLOWING:
  
 A. FLOOR PLAN SHOWING ALL IMPACTED DORM ROOMS. INDICATE
 GROUND FLOOR AND/OR ELEVATED FLOOR.
 B. DIMENSIONS OF THE DORM, BATHROOMS AND SHOWER
 ENCLOSURES
 C. DETAIL FOR SHOWER PAN (INCLUDE TYPE OF MATERIAL),
 CURB AND DRAIN COMPLYING WITH SHOWING COMPLIANCE WITH
 FBC PL SECTION 417.
 E. SPECIFICATION FOR SHOWER VALVE SHOWING COMPLIANCE
 WITH FBC PL 424.3. WHERE A HAND HELD SHOWER IS
 REQUIRED, COMPLY WITH FBC PL 424.2
 F. LOCATION OF EXISTING SERVICE SINK OR PROVIDE NEW
 SERVICE SINK TO SHOW COMPLIANCE WITH FBC PL TABLE 403.1
 G. PROVIDE ALL CLEAR FLOOR SPACES AND TURNING SPACES
 FOR ACCESSIBLE PLUMBING FIXTURES IN ACCORDANCE WITH FBC
 ACC SECTIONS 304 AND 305
 H. PROVIDE DETAILS FOR ACCESSIBLE FIXTURES SHOWING
 COMPLIANCE WITH FBC ACC CHAPTER 6.
 I. PER FBC ACC 806.2.4, PROVIDE AT LEAST ONE BATHROOM
 THAT IS PROVIDED AS PART OF A GUEST ROOM AND COMPLIES
 WITH 603. NO FEWER THAN ONE WATER CLOSET, ONE LAVATORY,
 AND ONE BATHTUB OR SHOWER SHALL COMPLY WITH APPLICABLE
 REQUIREMENTS OF 603 THROUGH 610. IN ADDITION, REQUIRED
 ROLL-IN SHOWER COMPARTMENTS SHALL COMPLY WITH 608.2.2
 OR 608.2.3. TOILET AND BATHING FIXTURES REQUIRED TO
 COMPLY WITH 603 THROUGH 610 SHALL BE PERMITTED TO BE
 LOCATED IN MORE THAN ONE TOILET OR BATHING AREA,
 PROVIDED THAT TRAVEL BETWEEN FIXTURES DOES NOT REQUIRE
 TRAVEL BETWEEN OTHER PARTS OF THE GUEST ROOM.
 J. PER FBC ACC 806.2.4.1, IF VANITY COUNTER TOP SPACE
 IS PROVIDED IN NON-ACCESSIBLE GUEST TOILET OR BATHING
 ROOMS, COMPARABLE VANITY COUNTER TOP SPACE, IN TERMS OF
 SIZE AND PROXIMITY TO THE LAVATORY, SHALL ALSO BE
 PROVIDED IN ACCESSIBLE GUEST TOILET OR BATHING ROOMS.
 K. PER FBC ACC 806.4, PLEASE NOTE THIS SECTION DOES NOT
 RELIEVE THE OWNER OF THE RESPONSIBILITY OF PROVIDING
 ACCESSIBLE ROOMS IN CONFORMANCE WITH SECTION 224 AND
 806 OF THIS CODE. IN ALL BUILDINGS, STRUCTURES AND
 FACILITIESLICENSED AS A HOTEL, MOTEL OR RESORT
 CONDOMINIUM PURSUANT TO CHAPTER 509, F.S., A NUMBER OF
 ROOMS EQUALING AT LEAST 5 PERCENT OF THE GUEST ROOMS
 MINUS THE TOTAL NUMBER OF REQUIRED (ACCESSIBLE) ROOMS
 REQUIRED BY TABLE 224.2 SHALL PROVIDE THE FOLLOWING
 ADDITIONAL SPECIAL ACCESSIBILITY FEATURES:
 (I) GRAB RAILS IN BATHROOMS AND TOILET ROOMS WHICH
 COMPLY WITH SECTION 604.5.
 (II) ALL BEDS IN DESIGNED ACCESSIBLE GUEST ROOMS SHALL
 BE OPEN-FRAME TYPE THAT ALLOWS THE PASSAGE OF LIFT
 DEVICES.
 (III) WATER CLOSETS THAT COMPLY WITH SECTION 604.4.
  
 2A. PER WPB FBC 107.1,ALL PLANS TO BE SIGNED AND SEALED
 BY THE DESIGNER IN ACCORDANCE WITH FAC AND FS. DESIGNER
 TO PROVIDE DIGITAL SIGNATURE IN ACCORDANC WITH FAC AND
 FS OR SHALL PROVIDE SIGNED AND SEALED PAPER DOCUMENT
 PRIOR TO PERMIT ISSUANCE.CALL 561-805-6724 FOR
 ADDITIONAL INFORMATION
 2B. SEE WPB FBC 107.3.4.3 CERTIFICATION BY CONTRACTOR.
 PLEASE NOTE THE EXCEPTION TO ENGINEERED PLANS UNDER
 471.003(H) ELECTRICAL/ PLUMBING/ MECHANICAL,
 481.229(1)(C) (BUILDING) REQUIRES THE CONTRACTOR FOR
 THAT TRADE THAT WILL BE LICENSED IN THAT TRADE, WILL
 ALSO BE THE CONTRACTOR THAT DESIGNS THE SYSTEM UNDER
 THAT TRADE. THE CONTRACTOR (QUALIFIER) THAT CREATED /
 DRAWN THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES
 AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME,
 SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE
 LICENSED IN AND PLANS DRAWN. FOR EACH TRADE THE
 CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER THE TRADE
 LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR NAME AND
 LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE DRAWN BY
 ONE INDIVIDUAL, THEY WOULD HAVE TO BE LICENSED AS A
 BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO SUBMIT
 ALL THESE TRADES UNDER ONE SHEET.
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20060009 2600 N MILITARY TRL
  