| 2020-06-18 14:38:43 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE A COMPLETE CONCRETE PAD DESIGN, THE |
| | ONE IN THIS SUBMITTAL WAS CUT OFF AND CAN ONLY SEE HALF |
| | OF THE DOCUMENT. FBC FS 107.2.1 |
| | |
| | 2) PLEASE SHOW THE SIZE OF THE PIPE AND THE MATERIAL OF |
| | THE PIPE LEAVING THE METER AND SUPPLYING THE GAS LOAD |
| | TO THE HOUSE. FBC FS 107.2.1 |
| | |
| | 3) IS THE EXISTING GAS SERVICE A 2 PSI SYSTEM? IF SO, |
| | PLEASE SHOW THE MP REGULATOR FOR THE APPLIANCES. FBC FS |
| | 107.2.1 |
| | |
| | 4) WHAT TYPE OF CONNECTION IS BEING USED BETWEEN THE PE |
| | PIPING AND THE GENERATOR? IF A HOSE IS USED PLEASE |
| | PROVIDE THE SPECS AND IDENTIFY THE HOSE USED. PLEASE |
| | SHOW PRESSURE DROP. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |