| 2020-06-17 15:33:28 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20051001 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE ADD THE VALUE OF THIS PROJECT TO THE GAS SUB |
| | PERMIT. FBC FS 107.2.1 |
| | |
| | 2) INTERIOR IS EXISTING LOW PRESSURE SYSTEM, THE METER |
| | IS GOING TO BE UPGRADED TO A 2PSI SYSTEM. WHERE IS THE |
| | MP REGULATOR FOR THE INTERIOR PIPING SYSTEM MAKING IT A |
| | LOW PRESSURE SYSTEM? FBC FS 107.2.1 |
| | |
| | 3) HOW IS THE ?? PE PIPING CONNECTING TO THE GENERATOR? |
| | IF A HOSE IS TO BE USED FOR THIS CONNECTION, PLEASE |
| | PROVIDE SPEC SHEETS FOR THIS HOSE. PLEASE IDENTIFY |
| | WHICH HOSE IS TO BE USED ALONG WITH THE PRESSURE DROP. |
| | FBC FS 107.2.1 |
| | |
| | 4) PROVIDE A DETAIL DRAWING OF THE NEW METER WITH THE |
| | 2PSI REGULATOR AND THE PIPING TO THE BRANCHES TO THE |
| | GENERATOR, THE FUTURE POOL AND THE EXISTING HOUSE LOW |
| | PRESSURE SYSTEM. PLEASE SHOW PIPE SIZES, REGULATOR AND |
| | FITTINGS . FBC FS 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |