| Plan Review Notes For Permit 20050999 |
| Permit Number |
20050999 |
|
| Review Stop |
SIGNATURE |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2020-08-22 09:45:05 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | SIGNATURE REVIEW DENIED: | | | | | | THE SUBMITTED DIVERSITECH CONCRETE PAD ENGINEERING IS | | | SIGNED/SEALED BY RICHARD NEET OF ENGINEERING EXPRESS. | | | THIS CONCRETE PAD DETAIL DOES NOT GIVE THE SPECIFIC | | | WINDLOAD INFORMATION AND THE GENERATOR SIZE IS NOT | | | INCLUDED ON THIS SCHEDULE AS OTHER SUBMITTED PLAN PAGES | | | DESCRIBE THIS GENERATOR AS A GENERAC 32KW. | | | | | | THE EARLIER SUBMITTED GENERATOR PAD ENGINEERING DETAILS | | | ARE NOT FROM DIVERSITECH BUT FROM AMERITECH AND APPEAR | | | TO HAVE THE REQUIRED INFORMATION BUT HAVE A NON | | | VERIFIABLE SIGNATURE/SEAL BY FRANK BENNARDO OF | | | ENGINEERING EXPRESS. |
|