| 2020-06-17 14:18:31 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT -20050999 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE SPEC SHEETS FOR THE REGULATORS. FBC FS |
| | 107.2.1 |
| | |
| | 2) THE INTERIOR GAS SYSTEM IS A LOW PRESSURE SYSTEM, |
| | THE NEW REGULATOR AT THE METER IS A 2PSI REGULATOR |
| | MAKING THIS ENTIRE SYSTEM A 2PSI SYSTEM. WHERE IS THE |
| | MP REGULATOR FOR THE INTERIOR GAS SYSTEM? AGAIN, THE |
| | REGULATOR AT THE METER IS 2 PSI. WHY IS THERE ANOTHER |
| | 2PSI REGULATOR AT THE NEW GENERATOR? SHOULDN?T THIS BE |
| | AN MP REGULATOR? PLEASE PROVIDE THE GAS TABLES USED FOR |
| | BOTH THE LOW PRESSURE AND 2PSI SYSTEMS. FBC FS 107.2.1 |
| | |
| | 3) HOW IS THE GENERATOR BEING CONNECTED TO THE ?? PE? |
| | IF A FLEXIBLE HOSE IS TO BE USED PLEASE SUPPLY SPECS. |
| | FOR THE HOSE AND LABEL THE HOSE TO BE USED ON THE SPEC |
| | SHEET ALONG WITH THE PRESSURE DROP. FBC FS 107.2.1 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |