| 2020-07-30 16:59:42 | 07/30/20 2ND GAS/ REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF |
| | EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2. |
| | |
| | 2. PLEASE SHOW AND LABEL DRIP LEG ON EQUIPMENT |
| | INSTALLED IF INSIDE GENERATOR MAKE NOTE PER THE 2017 |
| | FBC RES. SEC. G2419.2. |
| | |
| | 3. PLEASE SHOW THE SHUTOFF VALVE ON GAS ISOMERIC PER |
| | THE 2017 FBC FG SEC. 409.4 OR 2017 FBC RES. SEC. |
| | G2401.1.3. |
| | |
| | 4. PLEASE SHOW AND LABEL THE REGULATOR ON GAS ISOMERIC |
| | PER THE 2017 FBC FG SEC. 409.4 OR 2017 FBC RES. SEC. |
| | G2401.1.3. |
| | |
| | 5. PLEASE SHOW THE PE LINES ON THE SIDE OF EXIT ON THE |
| | METER NOT THE INLET PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 6. THE GENERATOR ON THE ISOMETRIC SAYS 27 KW, PLEASE |
| | CHANGE TO BTU'S AND BELOW YOU HAVE 330 BTU'S WHICH AT |
| | FULL LOAD A 27 KW SHOULD BE 359 BTU'S SO RECALCULATE |
| | AND CHANGE TOTAL BTU'S PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |