| Plan Review Notes For Permit 20050970 |
| Permit Number |
20050970 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-06-30 12:50:06 | 1) THE SUBMITTED IRRIGATION PLANS REFERENCE A PVB | | | (PRESSURE VACUUM BREAKER) BACKFLOW PREVENTER BUT | | | SPECIFICATIONS HAVE BEEN SUBMITTED FOR AN IRRITROL | | | VALVE WHICH IS NOT A PRESSURE VACUUM BREAKER. CLARIFY. | | | 2) IF A PRESSURE VACUUM BREAKER IS BEING INSTALLED, | | | SUBMIT SPECIFICATIONS FOR THE DEVICE BEING INSTALLED. | | | THE DEVICE MUST BE LEAD FREE AND BE ON THE LIST OF | | | APPROVED DEVICES THAT ARE APPROVED BY THE UNIVERSITY OF | | | SOUTHERN CALIFORNIA FOUNDATION FOR CROSS CONNECTION | | | CONTROL AND HYDRAULIC RESEARCH. | | | 3) HEADS SHALL BE LOCATED A MINIMUM OF ONE FOOT FROM | | | THE EXTERIOR WALL OF THE BUILDING. | | | 4) THE IRRITROL ATMOSPHERIC VACUUM BREAKER" VALVE SHALL | | | BE LOCATED A MINIMUM OF 6 INCHES ABOVE THE HIGHEST | | | SPRINKLER HEAD. | | | NOTE: IF YOUR INTENT IS TO INSTALL THE IRRITROL VALVE | | | THEN REMOVE ANY REFERENCE TO THE "PVB" ACRONYMN FROM | | | THE PLAN AND A SEPARATE PERMIT IS NOT REQUIRED FOR THE | | | INSTALLATION AND THE DEVICE CAN BE INSTALLED BY AN | | | IRRIGATION CONTRACTOR, HOMEOWWNER, ETC. YOUR PLAN IS | | | VERY CONFUSING. PLEASE CLARIFY AND SUBMIT A REVISED | | | PLAN. | | | FYI - THE IRRITROL VALVE IS EQUIPPED WITH AN | | | "ATMOSPHERIC VACUUM BREAKER" WHICH IS QUITE DIFFERENT | | | FROM A "PVB". | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|