| 2021-01-07 07:35:42 | PLAN REVIEW / BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NEC 2014 |
| | |
| | 2ND REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. SHUTTER PRODUCT APPROVAL IS ILLIGIBLE. RE-SUBMIT. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | 2. SCHEDULE FOR OPENING PROTECTION DEVICES (WINDOW AND |
| | DOOR DESIGN FORM) AND ENGINEERED FASTENER DESIGN |
| | SPECIFICATIONS SUBMITTED FOR REVIEW ARE MISSING THE |
| | FOLLOWING INFORMATION: |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 2A) TYPE OF CONSTRUCTION |
| | 2B) TYPE OF PROTECTIVE DEVICE - PERMAMENT/REMOVABLE |
| | 2C) BUILDING HEIGHT |
| | 2D) SHUTTER/GLASS SEPERATION |
| | 2E) SHUTTER INSTALLED - VERTICALL/HORIZONTAL |
| | 2F) MINIMUM EDGE DISTANCE OF FASTENERS |
| | 2G) BUILDING SUBSTRATE |
| | 2H) CENTER BOLT REQUIRED - Y/N |
| | |
| | |
| | RECOMMEND THE USE OF THE CITY'S SHUTTER SCHEDULE. |
| | |
| | NOTICE: YOU MAY REQUEST A COPY OF THE CITY'S SHUTTER |
| | SCHEDULE UPON REQUEST. SEE E-MAIL ABOVE. |
| | |