| Plan Review Notes For Permit 20050913 |
| Permit Number |
20050913 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-06-04 15:30:03 | CODE REFERENCE FOR BELOW NOTES IS FBC FS 107.2.1 | | 2020-06-04 15:26:20 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT-20050913 | | | | | | CODES IN EFFECT: | | | | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE SCOPE OF WORK. THE DRAWING SUBMITTED | | | IS AN APPROVED COPY FROM 1/10/2002. THIS DRAWING IS | | | SHOWING A NEW AHU AND A/C UNIT INCLUDED AS THE SCOPE OF | | | WORK. PLEASE PROVIDE A DRAWING WITH ONLY THE WORK BEING | | | COMPLETED IN THIS PROJECT. PROVIDE INFORMATION ON THE | | | DUCTS; SIZES AND INSULATION. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|