| Plan Review Notes For Permit 20050907 |
| Permit Number |
20050907 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-06-01 09:19:29 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE HORIZONTAL ROLLING WINDOWS IN THE BEDROOMS THAT | | | ARE MARKED EGRESS DO NOT APPEAR TO COMPLY WITH FBC-R | | | 310 FOR THE REQUIRED CLEAR OPENING WIDTH OF 22 INCHES. | | | FBC-R 310.2.5 ALLOWS REPLACEMENT WINDOWS THAT ARE THE | | | MANUFACTURER'S LARGEST STANDARD SIZE THAT WILL FIT IN | | | THE ROUGH OPENING AND IS THE SAME OPERATING STYLE AS | | | THE EXISTING WINDOW OR A STYLE THAT PROVIDES EQUAL OR | | | GREATER OPENING AREA THAN THE EXISTING WINDOW. EXPLAIN | | | HOW THIS REQUIREMENT IS BEING MET. | | | | | | |
|