Plan Review Notes
Plan Review Notes For Permit 20050904
Permit Number 20050904
Review Stop P
Sequence Number 2
Notes
Date Text
2020-08-20 16:10:2320050904 2995 45TH ST
  
  
 PLUMBING COMMENTS: APPROVED
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
 A SEPARATE PERMIT IS REQUIRED FOR BACKFLOW DEVICES
  
 PROVISO:
 RPZ APPEARS TO BE IN MIDDLE OF PARKING LOT DRIVE
 THROUGH. THE DEVICE SHALL BE LOCATED ABOVE GRADE PER
 FBC PL 608.13.2 AND PROTECTED FROM TRAFFIC (AND SHALL
 NOT IMPEDE THE FLOW OF TRAFFIC). BFP DETAIL SHOWN ON
 C8.3 DOES NOT REFLECT THIS. DETAIL SHOWN IS NOTED FOR
 INDOOR INSTALLATION. PIPING FOR THE BACKFLOW DEVICE
 SHALL BE TYPE "K" OR "L" COPPER, BRASS OR STAINLESS
 STEEL PER THE CITY OF WEST PALM BEACH CROSS CONNECTION
 CONTROL MANUAL. THE DEVICE SHALL BE LOCATED A MINIMUM
 OF 18 INCHES ABOVE FINISH GRADE TO THE RELIEF VALVE.
 PER WPB FBC 107.2.1, REROUTE PIPING AND RELOCATE RPZ TO
 COMPLY WITH THE ABOVE. RECONCILE FINAL DRAWINGS C8,
 C8.3 AND SD1 IN MASTER PERMIT 20050889 AND 20050904.
 PROVIDE REVISION PRIOR TO FIRST INSPECTION. PROCEED AT
 YOUR OWN RISK.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  