| Plan Review Notes For Permit 20050899 |
| Permit Number |
20050899 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-06-16 11:00:48 | PARKING LOT LIGHTING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE SIGNED AND SEALED LIGHT POLE DETAILS | | | SHOWING ATTACHMENT TO FOUNDATION AND THE WIND DESIGN | | | PARAMETERS USED TO COMPLY WITH FBC 1609. SIGNED AND | | | SEALED DOCUMENTS OR DRAWINGS NEED TO BE ELECTRONICALLY | | | SIGNED AND SEALED TO BE USED IN ELECTRONIC PLAN REVIEW. |
|