| 2020-08-31 14:48:13 | 1) SHT. A3.5 - THERE IS A NOTE UNDER THE FIXTURE COUNT |
| | TABLE THAT STATES" A BEVERAGE FOUNTAIN WITH DRINKING |
| | WATER OFFERING IS USED TO SATISFY THE DRINKING FOUNTAIN |
| | REQUIREMENT." REMOVE THIS NOTE FROM THE PLAN AS IT DOES |
| | NOT MEET THE REQUIREMENT FOR DRINKING FOUNTAINS. 2ND |
| | REQUEST. |
| | 2) SHT. SD2 - GREASE INTERCEPTOR DETAIL - SHOW THE |
| | HEIGHT OF THE TEE MANIFOLD AND VENT SLEEVE FROM THE |
| | FLOOR OF THE INTERCEPTOR. THE DETAIL SHOWS 0.6-0.7 FL1. |
| | I HAVE NO IDES WHAT THIS MEANS. SHOW THE DIMENSION IN |
| | INCHES.WPB AMEND.TO FBC SEC. 107.2.1. |
| | 3) SHT. C8 REFERS TO SHT. C8.3 FOR A DETAIL FOR A 3/4 |
| | INCH BACKFLOW DETAIL. THERE IS NO SUCH DETAIL ON SHT. |
| | C8.3. IN ADDITION, THE REFERENCED WILKINS 975 XL IS NOT |
| | A LEAD FREE DEVICE AS REQUIRED BY THE CITY OF WPB |
| | CROSS-CONNECTION CONTROL MANUAL. |
| | 4) SHT. P2.2 - SHOWS A HOUSE TRAP ON THE GREASE WASTE |
| | SYSTEM. HOUSE TRAPS ARE PROHIBITED PER FBC-PLUMBING |
| | SEC.1002.6. |
| | 5) SHT. P2.2 - IDENTIFY THE STANDARD THAT WAS USED IN |
| | THE SIZING CALCULATIONS FOR THE GREASE TRAP. |
| | 6) SHT. SD2 - GREASE TRAP CALCULATIONS - THE |
| | CALCULATIONS SHOW 128.16 GPM FLOW RATE AND ALSO 144.68 |
| | GPM. CLARIFY. ALSO, WHAT IS THE 7 MINUTE TIME THAT IS |
| | IN THE EQUATION? PLEASE EXPLAIN THESE CALCULATIONS. WPB |
| | AMEND TO FBC SEC. 107.2.1. |
| | 7) SHT. IP 200 - DETAIL #10 - THE BACKFLOW DEVICE SHALL |
| | BE LOCATED A MINIMUM OF 18 INCHES ABOVE FINISH GRADE TO |
| | THE RELIIEF PORT, NOT TO THE BODY OF THE VALVE AS SHOWN |
| | PER CITY OF WPB CROSS-CONNECTION CONTROL MANUAL. |
| | 8) SHT.P2.2 - DRAINS FROM THE ICE MAKERS ARE SHOWN |
| | DISCHARGING TO THE GREASE WASTE SYSTEM. IF THIS IS |
| | CLEAR WATER WASTE, IT CANNOT DISHARGE TO THE GREASE |
| | WASTE SYSTEM. FBC-PLUMBING SEC.1003.2. |
| | 9) SHT. P2.2 SHOWS A 1/2 INCH LINE FROM A ROOF HYDRANT |
| | DISCHARGING TO THE GREASE WASTE SYSTEM. WHY IS THIS |
| | DISCHARGING TO THE GREASE WASTE SYSTEM? CLARIFY. |
| | 10) THE RESPONSE NARRATIVE STATES THAT THE WASTE FROM |
| | THE COLD PAN (COFFEE), COLD PAN (HOT DOG), SANDWICH |
| | COOLERS, BILLET IMPULSE COOLER, COUNTER DRAINS, AND |
| | YOGURT TABLE WILL BE CONDENSATE. SOME OF THESE DRAINS |
| | ARE DISCHARGING TO THE SANITARY AND SOME ARE GOING TO |
| | THE GREASE WASTE SYSTEM. CONDENSATE SHALL NOT DISCHARGE |
| | TO THE GREASE WASTE SYSTEM PER FBC- PLUMBING SEC. |
| | 1003.2. |
| | 11) UNCONTAMINATED COOLING WATER OR AIR CONDITIONING |
| | CONDENSATE SHALL NOT DISCHARGE TO THE SANITARY SYSTEM |
| | UNLESS SPECIFICALLY AUTHORIZED BY THE CITY IN WRITING |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES CHAPTER |
| | 90, ARTICLE III, SEC. 90-126 (B) (5). |
| | 12) SHT. P3.2 WATER MANIFOLD/FILTER DETAIL - THERE IS A |
| | NOTE STATING THE A BACKFLOW PREVENTION DEVICE IS |
| | INSTALLLED IN A BOX AT STREET. CLARIFY. BACKFLOW |
| | DEVICES ARE NOT PERMITTED TO BE INSTALLED BELOW GRADE |
| | PER THE CITY OF WEST PALM BEACH CROSS CONNECTION |
| | CONTROL MANUAL. |
| | 13) SHT. P3.2 - INDICATE THE TYPE OF BACKFLOW DEVICE ON |
| | THE WATER BOOSTER. THE ISOMETRIC DRAWING NOTES "CHECK |
| | VALVE. TYPICAL." |
| | 14) IF THE HOSE REEL AND RINSE-O-MMATIC HAVE HOSE |
| | CONNECTIONS, THE TYPE OF BACKFLOW DEVICE SHALL BE A |
| | VACUUM BREAKER COMPLYING WITH ASSE 1011 PER |
| | FBC-PLUMBING TABLE 608.1. |
| | 15) SHT. P3.1 - NOTE #17 - THE HAND SINKS SHALL HAVE |
| | HOT WATER PER FBC-PLLUMBING SEC.607.1. PUBLIC |
| | LAVATORIES SHALL HAVE TEMPERED WATER PER FBC-PLUMBING |
| | SEC.416..5. |
| | 16) SHT. A10.1 - ROOF VENT NOTES - THE PLUMBING VENT |
| | SHALL BE AT LEAST 3 FEET OR MORE ABOVE THE TOP OF THE |
| | OPENING, NOT 2 FEET AS NOTED. REVISE THE NOTE. |
| | FBC-PLUMBING SEC.903.5. |
| | 17) SHT. P4.1 - THIS PLAN IS NOT DIGITALLY SIGNED OR |
| | SEALED PER FL. ADMIN. CODE RULE 61G15-23.004, |
| | 61G15-23.005. |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |