| 2020-07-10 08:51:28 | 1) AS OF APRIL 16, 2015 THE MINIMUM ENERGY FACTOR OF |
| | WATER HEATERS WITH A VOLUME AT OR BELOW 55 GALLONS SHAL |
| | BE .95. THE ENERGY CALCULATIONS SHOW AN EFFICIENCY OF |
| | .84. SUBMIT NEW ENERGY CALCULATIONS WITH THE REVISED |
| | WATER HEATER EFFICIENCY. |
| | 2) SHT.A10.1 - THE CALCULATIONS FOR THE ROOF DRAIN |
| | LEADERS SHALL INCLUDE ONE-HALF THE AREA OF ANY VERTICAL |
| | WALL PER 2017 FBC-PLUMBING SEC.1106.4. INCLUDE THESE |
| | CALCULATIONS ON THE SHEET. |
| | 3) THE RAIN LEADERS SHALL DISCHARGE A MINIMUM OF ONE |
| | FOOT FROM THE EXTERIOR BUILDING WALL PER FBC-BUILDING |
| | SEC.1503.7. |
| | 4) SHT. A10.1 - THE PLANS NOTE THE OVERFLOW SCUPPERS |
| | DIMENSIONS AS 3 X 5 INCHES. SCUPPERS SHALL HAVE AN |
| | OPENING NOT LESS THAN 4 INCHES. PER FBC- PLUMBING SEC. |
| | 1108.3. |
| | 5) SHT. A10.4 - DETAIL "J" - SHOWS THE SCUPPER SIZE AS |
| | 4 X 12 INCHES AND SHT. A10.1 SHOWS THE SIZE AS 4 X 9 |
| | INCHES. CLARIFY. |
| | 6) SHOW THE DIMENSIONS OF THE CLEAR FLOOR SPACES FOR |
| | THE HANDICAP ACCESSIBLE FIXTURES ON SHT. A3.2. COMPLY |
| | WITH FBC-ACCESSIBILITY SECS. 305.3, 604.3.1, 606.2. |
| | 7) SHT. A3.5 - NOTE UNDER FIXTURE COUNT TABLE STATES |
| | THAT A BEVERAGE FOUNTAIN WITH DRINKING WATER OFFERING |
| | IS USED TO SATISFY THE DRINKING FOUNTAIN REQUIREMENT IS |
| | UNACCEPTABLE. THE SAME NOTE APPEARS ON SHT.GC-0.0. |
| | TABLE 403.1 OF THE FBC-PLUMBING REQUIRES A DRINKING |
| | FOUNTAIN FOR THIS OCCUPANCY AND SEC. 410.3 OF THE |
| | PLUMBING CODE AND SEC. 211.2 OF THE ACCESSIBILITY CODE |
| | CLEARLY STATES THAT A MINIMUM OF TWO DRINKING FOUNTAINS |
| | ARE REQUIRED. SHOW THE LOCATION OF THE DRINKING |
| | FOUNTAINS ON THE PLANS AND THE REQUIRED CLEAR FLOOR |
| | SPACE FOR THE FOUNTAINS. |
| | 8) SHT. A3.5 - ADA COUNTER REACH RANGES SHALL COMPLY |
| | WITH FBC-ACCESSIBILITY SECS.3308.2, 308.2.1, 308.2.2, |
| | 308.3, 308.3.2. THE DETAIL ON THE PLAN DOES NOT COMPLY. |
| | 9) SHT. A5.3 - THE HEIGHT OF THE GRAB BARS SHALL BE |
| | MEASURED TO THE TOP OF THE GRIPPING SURFACE PER |
| | FBC-ACCESSIBILITY SEC. 609.4. |
| | 10) SUBMIT SIZING CALCULATIONS FOR THE GREASE |
| | INTERCEPTOR. FBC-PLUMBING SEC. 1003.2. NOTE: A SEPARATE |
| | PERMIT IS REQUIRED FOR THE INSTALLATION OF THE GREASE |
| | INTERCEPTOR. |
| | 11) SHOW THE HEIGHT OF THE TEE MANIFOLD AND VENT SLEEVE |
| | FROM THE FLOOR OF THE INTERCEPTOR. |
| | 12) THE INLET INVERT OF THE GREASE INTERCEPTOR SHALL |
| | DISCHARGE A MINIMUM OF 2 1/2 INCHES ABOVE THE LIQUID |
| | LEVEL LINE AND THE OUTLET TEE SHALL BE A MINIMUM OF 4 |
| | INCHES THAT EXTENDS TO WITHIN 8 INCHES OF THE BOTTOM OF |
| | THE TANK PER FL. ADMIN. CODE RULE 64E-6. |
| | 13) A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW |
| | DEVICES. |
| | 14) ALL BACKFLOW DEVICES SHALL BE LEAD FREE AND BE ON |
| | THE LIST OF APPROVED DEVICES OF THE UNIVERSITY OF |
| | SOUTHERN CALIFORNIA'S FOUNDATION FOR CROSS-CONNECTION |
| | CONTROL AND HYDRAULIC RESEARCH. |
| | 15) A PERMIT IS REQUIRED FROM PALM BEACH COUNTY |
| | DEPARTMENT OF ENVIRONMENTAL RESOURCE MANAGEMENT FOR THE |
| | FUEL TANKS. |
| | 16) SHT. A0.2 - PLUMBING NOTES - THERE ARE SEVERAL |
| | NOTES THAT REFER TO THE GENERAL CONTRACTOR PERFORMING |
| | THE INSTALLATION OF THE PLUMBING SYSTEM AND BACKFLOWW |
| | DEVICE. A GENERAL CONTRACTOR CANNOT PERFORM THIS SCOPE |
| | OF WORK UNLESS THEY ARE LICENSED AS A PLUMBING |
| | CONTRACTOR PER FL. STATUTE 489.105. THIS NOTE ALSO |
| | APPEARS ON SHT.GC-0.1 UNDER "PLUMBING RESPONSIBILITY". |
| | CLARIFY. |
| | 17) CLARIFY AS TO WHO IS MADISON INDUSTRIES? ARE THEY |
| | LICENSED CONTRACTORS IN THE STATE OF FLORIDA? PROVIDE |
| | INFORMATION. |
| | 18) THE GC SHEET ARE REQUIRED TO BE DIGITALLY SIGNED |
| | AND SEALED PER FL. ADMIN. CODE RULE 61G1-16.005. |
| | 19) SHTS. GC-2.2, GC-2.3, GC-3.0, GC-3.1, GC-4.0, |
| | GC-4.1 BEAR THE SEAL OF THE ARCHITECT BUT THE SEAL IS |
| | FOR THE STATE OF GEORGIA. CLARIFY. |
| | 20) SHT. IP 200 - DETAIL #10 - PVC AND GALVANIZED PIPE |
| | IS NOT APPROVED MATERIAL FOR THE PIPING FOR THE |
| | BACKFLOW DEVICE. TYPE "K" OR "L" COPPER, BRASS OR |
| | STAINLESS STEEL ARE THE APPROVED MATERIALS PER THE CITY |
| | OF WEST PALM BEACH CROSS CONNECTION CONTROL MANUAL. THE |
| | DEVICE SHALL BE LOCATED A MINIMUM OF 18 INCHES ABOVE |
| | FINISH GRADE TO THE RELIEF VALVE. |
| | 21) SHT. P1.1 - MANUFACTURING PLANT INSTALLATION |
| | NOTES#1 REFER TO "B.S." FOR THE INSTALLATION OF THE |
| | COMPLETE PLUMBING SYSTEM WITHIN THE MODULAR BUILDING. |
| | WHO IS "B.S."? CLARIFY. |
| | 22) CARBONATED BEVERAGE DISPENSERS SHALL BE EQUIPPED |
| | WITH BACKFLOW DEVICES SPECIFICALLY DESIGNED FOR |
| | CARBONATION EQUIPMENT AND SHALL COMPLY WITH ASSE 1022. |
| | 23) SHT. P1.1 - PIPE INSULATION SHALL COMPLY WITH |
| | FBC-ENERGY TABLE C403.2.10. |
| | 24) SHT. P1.1 - NOTE #7 - PVC PIPE SHALL BE HUNG AT 4 |
| | FEET INTERVALS HORIZONTALLY AND 10 FEET INTERVALS |
| | VERTICALLY PER FBC-PLUMBING TABLE 308.5. |
| | 25) SHT. P1.1 - NOTES REFER TO THE GENERAL CONTRACTOR |
| | PERFORMING PLUMBING WORK. A GENERAL CONTRACTOR MUST BE |
| | LICENSED AS A PLUMBING CONTRACTOR TO PERFORM THIS TYPE |
| | OF WORK. EITHER REVISE THE NOTE OR REMOVE IT. |
| | 26) HAND SINKS IN THE FOOD PREP AREA SHALL BE |
| | INDIRECTLY WASTED TO A WASTE RECEPTOR. FBC-PLUMBING |
| | SEC.802.1.1 |
| | 27) SHT. P2.1 - MASTER TRAP DETAIL - APPEARS TO BE A |
| | VERSION OF A CROWN VENT WHICH IS PROHIBITED BY THE |
| | FLORIDA PLUMBING CODE. DELETE THIS DETAIL. |
| | 28) SHT. P2.2 - THERE IS A FLAT, DRY VENT ON THE END OF |
| | THE RUN FOR THE FLOOR SINKS IN THE SALES FLOOR AREA. |
| | DRY VENTS CONNECTING TO A HORIZONTAL DRAIN SHALL |
| | CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN |
| | PIPE.905.3. |
| | 29) WHAT TYPE OF WASTE WILL BE DISCHARGING FROM THE |
| | COLD PAN (COFFEE) AND COLD PAN ( HOT DOG) DRAINS? |
| | 30) WHAT TYPE OF WASTE WILL BE DISCHARGING FROM THE |
| | SANDWICH COOLERS, THE BILLET IMPULSE COOLER AND THE |
| | COUNTER DRAINS? |
| | 31) THE DRAINS FROM THE YOGURT MACHINE AND YOGURT TABLE |
| | SHALL DISCHARGE TO THE GREASE WASTE SYSTEM IF THE |
| | DISCHARGE CONTAINS ANY YOGURT PRODUCT.FBC-PLUMBING |
| | SEC.1003.3.1. CLARIFY. |
| | 32) THE 2 INCH VENT BY THE MASTER TRAP IS A FLAT, DRY |
| | VENT.DRY VENTS CONNECTING TO A HORIZONTAL DRAIN SHALL |
| | CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN |
| | PIPE.905.3. |
| | 33) CONDENSATE VENTS CANNOT CONNECT TO THE SANITARY |
| | VENT SYSTEM PER FBC-PLUMBING SEC.901.4. |
| | 34) THE CLEANOUTS ON THE DRAIN LINES UNDER THE BUILDING |
| | SHALL BE EXTENDED TO THE FLOOR LEVEL PER FBC-PLUMBING |
| | SEC.708.1.10. |
| | 35) ACCESS IS REQUIRED FOR THE CLEANOUTS LOCATED BELOW |
| | FLOOR. FBC-PLUMBING SEC.708.1.10. |
| | 36) SHT. P2.2 - THE HUB DRAINS FOR THE COLD PAN |
| | (COFFEE) AND COLD PAN (HOT DOG) APPEAR TOEXCEED THE |
| | DISTANCE FROM A VENT PER FBC-PLUMBING SEC.909.1 AND |
| | TABLE 909.1. |
| | 37) SHT. P3.2 - THE WATER LINE TO THE ICE MACHINE IS |
| | LABELED AS FW1 BUT THE ICE MACHINE IS LABELED AS FW2. |
| | THE SAME ISSUE OCCURS ON THE WATER LINE TO THE BEVERAGE |
| | MACHINE.CLARIFY. |
| | 38) A BACKFLOW PREVENTION DEVICE IS REQUIRED ON THE |
| | WATER FILTRATION SYSTEM AND THE GLYCOL CHILLER PER |
| | FBC-PLUMBING SEC.608.3. THE DEVICE MUST BE INSTALLED AT |
| | THE WATER FILTER LOCATION. |
| | 39) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | COMBI-OVENS, WATER BOOSTER, RINSE-O-MATIC, FROZEN |
| | YOGURT DISPENSER AND POST MIX SODA SYSTEM. A BACKFLOW |
| | PREVENTION DEVICE IS REQUIRED ON THE WATER BOOSTER. |
| | 40) SHT. P3.2 - SIZE THE COLD WATER BRANCH LINE TO THE |
| | FEMALE RESTROOM. |
| | 41) BACKFLOW DEVICES ARE REQUIRED ON THE HOSE REEL & |
| | RINSE-O-MATIC. DEVICES SHALL COMPLY WITH TABLE 608.1 OF |
| | FBC-PLUMBING. |
| | 42) SHT. C8 - THERE IS A NOTE ON THE SHEET THAT REFERS |
| | TO SHT.C8.1 FOR A BACKFLOW DEVICE DETAIL. THERE IS NO |
| | DETAIL ON C8.1. CLARIFY. |
| | 43) SHOW THE LOCATION OF THE RINSE-O-MATIC ON THE WATER |
| | RISER. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 44) SHOW THE LOCATION OF THE GLYCOL CHILLER ON THE |
| | EQUIPMENT PLAN AND LIST IT ON THE EQUIPMENT SCHEDULE. . |
| | ENSURE ALL EQIPMENT IS LISTED ON THE EQUIPMENT SCHEDULE |
| | AND SHOWN ON THE EQUIPMENT PLAN.WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 45) THE HOT WATER RECIRCULATION SYSTEM SHALL COMPLY |
| | WITH FBC-PLUMBING SEC.607.2.1 & FBC-ENERGY |
| | SEC.C404.6.1. |
| | 46) SHT. C8 SHOWS A 2 INCH WATER SERVICE WITH A 1 1/2 |
| | INCH BACKFLOW PREVENTION DEVICE. CLARIFY. |
| | |