| 2020-07-06 15:37:28 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20050889 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE VENTILATION CALCULATIONS. FBC M TABLE |
| | 403.3.1.1 |
| | |
| | 2) PROVIDE SPEC SHEETS FOR EACH RTU. FBC FS 107.2.1 |
| | |
| | 3) PLEASE PROVIDE SPEC SHEETS FOR THE BATH EXHAUST |
| | FANS. FBC FS 107.2.1 |
| | |
| | 4) PLEASE PROVIDE SPEC SHEETS FOR ALL COOKING |
| | EQUIPMENT. FBCFS 107.2.1 |
| | |
| | 5) ALL WALK IN FREEZERS, COOLERS AND REFRIGERATION MUST |
| | BE SUBMITTED IN ANOTHER SUBMITTAL AND PERMITTED |
| | SEPARATELY. PLEASE INCLUDE ALL SPEC. SHEETS FOR EACH |
| | PIECE OF EQUIPMENT AND REFRIGERATION CALCULATIONS AT |
| | THAT TIME. FBC FS 107.2.1 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |