| Plan Review Notes For Permit 20050839 |
| Permit Number |
20050839 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-09-15 14:57:09 | SFR ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) CANNOT USE A "NAMI" APPROVED CERTIFICATION FOR THE | | | SINGLE HUNG WINDOWS. MUST USE A MIAMI DADE OR FLORIDA | | | STATE APPROVED PRODUCT APPROVAL. PLEASE PROVIDE | | | COMPLETE (FRONT PAGES AND THE INSTALLATION | | | INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE PRODUCT | | | APPROVALS FOR THE NEW EXTERIOR WINDOWS, ROOFING SYSTEM | | | TO BE USED ETC.. PRODUCT APPROVALS NEED TO BE REVIEWED | | | AND MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD | | | (ARCHITECT). | | | | | | 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVALS FOR THE ROOFING SYSTEM TO BE USED. | | | PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE | | | PRODUCT APPROVAL - IF NEEDED PLEASE PROVIDE SIGNED AND | | | SEALED ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT | | | OR ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY | | | REQUIRE A HIGHER WIND PRESSURE - SEE NOTES ON THE | | | PRODUCT APPROVAL. | | | |
|