| 2020-07-15 09:34:29 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20050839 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-1: PLEASE PROVIDE THE ENERGY CALCS AND THE |
| | MANUAL J FOR THE NEW MECHANICAL SYSTEM. FBC EC |
| | 101.5.1.1.2 |
| | |
| | 2) PLEASE SHOW RETURN AIR PATH FOR THE PROPOSED FAMILY |
| | ROOM. FBC RES M1602.3 |
| | |
| | 3) PLEASE SHOW TERMINATION FOR THE DRYER DUCT. PLEASE |
| | PROVIDE THE DEVELOPED LENGTH OF THE DRYER DUCT. FBC FS |
| | 107.2.1 |
| | |
| | 4) PLEASE PROVIDE INFORMATION FOR THE BATH EXHAUST FANS |
| | AND THE LOCATION OF EXTERIOR TERMINATION. FBC FS |
| | 107.2.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |