| 2020-07-29 11:28:47 | 3RD REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20050837 |
| | 7/29/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017C |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENTS LISTED BELOW FROM THE 1ST AND 2ND REVIEWS HAVE |
| | NOT BEEN COMPLETELY ADDRESSED. ADDITIONAL NOTES IN |
| | CAPITAL LETTERS HAVE BEEN PLACED AT THE END OF EACH |
| | COMMENT FOR FURTHER EXPLANATION OF THE PLAN |
| | DEFICENCIES. |
| | |
| | 2) SHEET A3.0: PROVIDE ENLARGED DIMENSIONED TOILET ROOM |
| | FLOOR PLANS AND DETAILS SHOWING COMPLIANCE WITH THE |
| | FBC-17 ACCESSIBILITY. (THE ENLARGED DRAWING SHOWS AN |
| | INCORRECT 48"X66" CLEAR FLOOR SPACE FOR THE WATER |
| | CLOSET- CLEARANCE AROUND A WATER CLOSET SHALL BE 60 |
| | INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM |
| | THE REAR WALL- 60"X56".) |
| | |
| | 3B) A3.0: TOE CLEARANCES FOR THE LAVATORY NOT SHOWN - |
| | SECTION 306. (NOT PROVIDED) |
| | |
| | 4) A1.0 & A3.0: REFER TO SECTION 211.1.2 FBC ACC, AND |
| | TABLE 404.3 FBC P. NO FEWER THAN TWO DRINKING FOUNTAINS |
| | SHALL BE PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY |
| | WITH SECTIONS 602.1- 602.6, AND ONE SHALL COMPLY WITH |
| | 602.7. SECTION 602.7 REQUIRES THAT SPOUT OUTLETS FOR |
| | STANDING PERSONS SHALL BE 38 INCHES MINIMUM AND 43 |
| | INCHES MAXIMUM FROM THE FINISHED FLOOR. PLEASE PROVIDE: |
| | A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR |
| | FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC. |
| | (CLEAR FLOOR SPACE DIAGRAM ON A1 DOES NOT SHOW |
| | DIMENSIONS) |
| | B) KNEE AND TOE CLEARANCES- SECTION 306. (NOT PROVIDED) |
| | |
| | 5) A1.0 & A3.0: THE NEW BREAKROOM SINK SHALL BE |
| | INSTALLED IN COMPLIANCE WITH SECTION 606 FBC ACC. |
| | PROVIDE DRAWINGS AND DETAILS. (CLEAR FLOOR SPACE |
| | PARALLEL APPROACH DIAGRAM ON A1 DOES NOT SHOW |
| | DIMENSIONS. A SIDE VIEW ELEVATION DETAIL OF THE |
| | BREAKROOM SINK SHOWING THE DEPTH OF THE COUNTER IS |
| | REQUIRED FOR REACH RANGE TO FAUCET COMPLIANCE- SECTIONS |
| | 308 & 309 FBC ACC.) |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. (RESPONSE LETTER NOT PROVIDED.) |
| | |