| 2020-08-02 09:34:54 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20050837 |
| | ADD: 2600 S. DIXIE HWY. / SUITE: D |
| | CONT: SEACOAST CONSTRUCTION |
| | TEL: 786-433-8740 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: SUN. AUGUST 02ND/ 2020 |
| | ACTION: DENIED |
| | |
| | *****************4X FEE / NOTICE!!!!! FLORIDA STATUTE |
| | 553.80(2)(B)******************* |
| | ARCHITECT JACK W. HUGENTUGLER R. A. 10097 |
| | TEL: 954-564-3044 |
| | |
| | |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | NO RESPONSE LETTER FROM ARCHITECT. |
| | |
| | 1) THE COVERSHEET: |
| | |
| | 1A) COMPLIED. |
| | |
| | 1B) COMPLIED. |
| | |
| | 2) THE LIFE SAFETY PLAN. |
| | 2A-B) COMPLIED. |
| | |
| | 2C) 3RD REQUEST. THE COVERSHEET DOES AND HAS SHOWN A |
| | SMALL SITE PLAN WHERE THE PROPERTY LINE IS SHOWN AT THE |
| | FRONT CORNER OF THE BUILDING. THE PLANS SHOW A OUTSWING |
| | DOOR. 2017 FBC-B 3202.2 DOORS AND WINDOWS SHALL NOT |
| | OPEN OR PROJECT INTO THE PUBLIC RIGHT OF WAY. |
| | |
| | 2D) 3RD REQUEST. SEMI- COMPLIED. THE SHEET A3.0 DETAIL |
| | 8 SHOWS AN ELEVATION VIEW WITH THE TOP OF THE COUNTER |
| | AT 42 INCHES. THE KNEE WALL/ END COUNTER IS SHOWN AT |
| | 2FEET 10 INCHES. THE RECEPTIONIST DESK TOP IS SHOWN ON |
| | THE LEFT SIDE OF THE DETAIL REVISION, # 2 AS 2FEET 6 |
| | INCHES BUT THERE IS ALSO SHOWN THE 4 INCH TOE KICK |
| | MAKING THE RECEPTIONIST DESK TOP 2 FEET 6 INCHES HIGH |
| | JUST AS HIGH AS THE KNEE WALL COUNTER TOP. DISCREPANCY |
| | IN PLANS. |
| | |
| | SEMI- COMPLIED CLEAR FLOOR SPACE IS NOW SHOWN ON THE |
| | LIFE SAFETY PLAN. SHEET ID 2.0 DETAIL 2 DOES SHOW A |
| | DROPPED SERVICE COUNTER AT A HEIGHT OF 2 FEET 10 |
| | INCHES, 34 INCHES, AND THE RECEPTION DESK TOP AT A |
| | HEIGHT OF 2 FEET 6 INCHES OR 30 INCHES. A DISCREPANCY |
| | WITH SHEET A3.0 DETAIL 8. |
| | . |
| | 2E) COMPLIED. THE NEW RTU UNIT TO BE PLACED IN THE |
| | EXISTING ROOF TOP CURB. |
| | |
| | 2E)(1) COMPLIED. |
| | |
| | 2E)(2) 2ND REQUEST. SEMI-COMPLIED. THE 47 PAGE TRANE |
| | REPORT BY DOUGLAS RUGGIANO PE IS NOT SIGNED WITH A |
| | DIGITAL SIGNATURE. 61G15-23.005 PROCEDURES FOR SIGNING |
| | AND SEALING ELECTRONICALLY TRANSMITTED PLANS (DIGITAL |
| | SIGNATURES), SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS. |
| | |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| | SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE |
| | OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON |
| | DIGITALLY SIGNED AND SEALED ENGINEERING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | REPORTS. 61G15-23.002(2)(B) FL. ADMIN. CODE. A COVER |
| | SHEET WITH LISTED PAGES OR INDEX SHEET FOR ENGINEERING |
| | SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE |
| | SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION & |
| | PREPARATION OF EACH SECTION OF THE ENGINEERING |
| | SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER |
| | SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER |
| | THE COVER SHEET OR INDEX SHEET. |
| | |
| | LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP |
| | EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS, |
| | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| | |
| | 2E)(3) NO RESPONSE FROM ARCHITECT 3RD REVIEW.2017 FBC-B |
| | 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL MEMBERS AND |
| | THEIR CONNECTIONS SHALL BE DETERMINED BY METHODS OF |
| | STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM, |
| | GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH |
| | SHORT- AND LONG-TERM MATERIAL PROPERTIES. EVERY |
| | STRUCTURE SHALL BE DESIGNED TO RESIST THE OVERTURNING |
| | EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED IN THIS |
| | CHAPTER. SEE SECTION 1609 FOR WIND LOADS. |
| | |
| | 2E)(4) NO RESPONSE FROM THE ARCHITECT 3RD REVIEW. 2017 |
| | FBC-M 306.5 EQUIPMENT AND APPLIANCES ON ROOFS OR |
| | ELEVATED STRUCTURES. |
| | WHERE EQUIPMENT REQUIRING ACCESS OR APPLIANCES ARE |
| | LOCATED ON AN ELEVATED STRUCTURE OR THE ROOF OF A |
| | BUILDING SUCH THAT PERSONNEL WILL HAVE TO CLIMB HIGHER |
| | THAN 16 FEET (4877 MM) ABOVE GRADE TO ACCESS SUCH |
| | EQUIPMENT OR APPLIANCES, AN INTERIOR OR EXTERIOR MEANS |
| | OF ACCESS SHALL BE PROVIDED. SUCH ACCESS SHALL NOT |
| | REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 |
| | INCHES (762 MM) IN HEIGHT OR WALKING ON ROOFS HAVING A |
| | SLOPE GREATER THAN 4 UNITS VERTICAL IN 12 UNITS |
| | HORIZONTAL (33-PERCENT SLOPE). SUCH ACCESS SHALL NOT |
| | REQUIRE THE USE OF PORTABLE LADDERS. WHERE ACCESS |
| | INVOLVES CLIMBING OVER PARAPET WALLS, THE HEIGHT SHALL |
| | BE MEASURED TO THE TOP OF THE PARAPET WALL. |
| | |
| | 2E)(5) SEMI- COMPLIED ONCE THE WIND REPORT CAN BE |
| | ACCEPTED. |
| | |
| | 2E)(6) NOT APPLICABLE. NO NEW ROOF OPENINGS, USE |
| | EXISTING CURB. |
| | |
| | 3) 2ND REQUEST. SHEET A3.0 ADA REQUIREMENTS: |
| | |
| | 3A) SEMI COMPLIED. 3RD REQUEST. THE DESIGNER OF RECORD |
| | CAN-NOT QUOTE THE CODE SECTION FOR COMPLIANCE. 2017 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 107.2.1. |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 2ND REQUEST. DETAIL # 3 MAKES REFERENCE TO THE FLORIDA |
| | BUILDING CODE CHAPTER 11. PLEASE REFER TO THE 2017 |
| | FBC-B CHAPTER 11 1102-1111 ARE RESERVED. UNDER THE 2017 |
| | FBC-ACCESSIBILITY CODE IT IS A SEPARATE CODE BOOK JUST |
| | LIKE THE ENERGY CODE, AND EXISTING BUILDING CODE PLEASE |
| | UPDATE PLANS TO THE CURRENT 2017 CYCLE. 107.2.1.2 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3B) 3RD REQUEST. DETAIL # 4 NOTES THAT THE TOILET ROOM |
| | WATER CLOSET SHALL COMPLY WITH FBC SECTIONS 11-4.16.1 |
| | THRU.6 . AGAIN PLEASE UPDATE YOUR CODE SECTIONS TO THE |
| | 2017 FBC-ACCESSIBILITY CODE. |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1. |
| | W.P.B. ADMINISTRATIVE CODE/2017 DRAWINGS & |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| | THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR |
| | IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED |
| | AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION |
| | DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 3C-D) COMPLIED. |
| | |
| | 3E) 3RD REQUEST. THE PLANS DO NOT SHOW THE ELEVATION OF |
| | THE HIGH/ LOW DRINKING FOUNTAIN NOR COMPLIANCE WITH THE |
| | ACCESSIBILITY CODE 307.2 PROTRUSION LIMITS. OBJECTS |
| | WITH LEADING EDGES MORE THAN 27 INCHES AND NOT MORE |
| | THAN 80 INCHES ABOVE THE FINISH FLOOR SHALL PROTRUDE 4 |
| | INCHES OR LESS MAXIMUM HORIZONTALLY INTO THE |
| | CIRCULATION PATH. SKIRTS MAYBE REQUIRED TO BE APPLIED |
| | TO THE BOTTOM OF THE DRINKING FOUNTAIN. |
| | |
| | 3F) COMPLIED. 2ND REQUEST. THE LIFE SAFETY PLAN NEEDS |
| | TO 606.2 CLEAR FLOOR SPACE FOR THE BREAK ROOM SINK. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |