2020-07-24 08:16:522ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20050837
 7/24/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017C
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 BASED ON THE COMMENT RESPONSE NARRATIVE FROM BACH
 ENGINEERS IT APPEARS THAT SOME OF THE CORRECTED PLANS
 WERE NOT UPLOADED FOR REVIEW. COMMENTS LISTED BELOW
 FROM THE 1ST REVIEW STILL EXIST. ADDITIONAL NOTES IN
 CAPITOL LETTERS HAVE BEEN ADDED.
  
 1) PROVIDE PLUMBING FIXTURE CALCULATIONS IN ACCORDANCE
 WITH TABLE 403.3 FBC P. PROVIDE A SCHEDULE OR TABLE ON
 THE PLAN THAT INDICATES THE REQUIRED AND PROVIDED
 PLUMBING FIXTURES. (CALCULATIONS AND FIXTURE SCHEDULE
 NOT PROVIDED.)
  
 2) SHEET A3.0: PROVIDE ENLARGED DIMENSIONED TOILET ROOM
 FLOOR PLANS AND DETAILS SHOWING COMPLIANCE WITH THE
 FBC-17 ACCESSIBILITY. (THE ENLARGED DRAWING SHOWS AN
 INCORRECT CLEAR FLOOR SPACE FOR THE WATER CLOSET, CLEAR
 FLOOR SPACE DIMESNIONS AT LAV NOT SHOWN, TURNING CIRCLE
 DIAMETER NOT SHOWN).
  
 A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS-
 SECTION 604.3. (INCORRECT)
  
 B) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORIES-
 SECTION 606.2. (NOT PROVIDED)
  
 C) TURNING SPACE DIAMETERS- SECTION 304.3. (NOT
 PROVIDED)
  
 3) A3.0- PROVIDE THESE CORRECTIONS:
 A) THE HEIGHT OF THE WATER CLOSET SEAT SHALL BE 17-19"
 MEASURED FROM THE FINISHED FLOOR TO THE TOP OF THE
 SEAT- SECTION 604.4 FBC ACC. THE DRAWING SHOWS THE
 DIMENSION AT THE BOTTOM OF THE SEAT. (INCORRECT-
 DRAWING SHOWS THE DIMENSION TO THE RIM OF THE WATER
 CLOSET NOT THE SEAT.)
  
 B) SHOW THE KNEE AND TOE CLEARANCES FOR THE LAVATORIES-
 SECTION 306. (NOT PROVIDED)
  
 D) THE HEIGHT OF THE GRAB BARS SHALL BE 33" MINIMUM TO
 36" MAXIMUM ABOVE THE FINISHED FLOOR- SECTION 604.5 FBC
 ACC. THE DRAWING SHOWS THE DIMENSIONS AT THE CENTER OF
 THE BAR. (DIMENSIONS ARE SHOWN TO THE CENTERLINES OF
 THE BARS AND NOT TO THE TOPS OF THE GRIPPING SURFACES
 AS REQUIRED BY SECTION 609.4 FBC ACC.)
  
 4) A1.0 & A3.0: REFER TO SECTION 211.1.2 FBC ACC, AND
 TABLE 404.3 FBC P. NO FEWER THAN TWO DRINKING FOUNTAINS
 SHALL BE PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH SECTIONS 602.1- 602.6, AND ONE SHALL COMPLY WITH
 602.7. SECTION 602.7 REQUIRES THAT SPOUT OUTLETS FOR
 STANDING PERSONS SHALL BE 38 INCHES MINIMUM AND 43
 INCHES MAXIMUM FROM THE FINISHED FLOOR. PLEASE PROVIDE:
 (NOT PROVIDED)
 A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC.
 B) KNEE AND TOE CLEARANCES- SECTION 306.
 C) SPOUT HEIGHT AND SPOUT LOCATION- SECTION 602.4 AND
 602.5.
 D) MANEUVERING CLEARANCES AT THE DOORWAYS BY THE
 DRINKING FOUNTAINS- FIGURE 404.2.4.1.
 E) COMPLIANCE WITH PROTRUDING OBJECTS- SECTION 307.2
  
 5) A1.0 & A3.0: THE NEW BREAKROOM SINK SHALL BE
 INSTALLED IN COMPLIANCE WITH SECTION 606 FBC ACC.
 PROVIDE DRAWINGS AND DETAILS. (NOT PROVIDED)
  
 6) P1.0: TEMPERED WATER IS REQUIRED AT THE LAVATORIES-
 SECTION 416.5 FBC P. PLEASE INDICATE HOW THIS
 REQUIREMENT WILL BE MET. PLEASE NOTE THAT TEMPERATURE
 LIMITING DEVICES SHALL CONFORM TO ASSE 1070- SECTION
 607.1.2 FBC P. (NOT PROVIDED)
  
 7) SHEET P1.0: PROVIDE A PLUMBING FIXTURE AND DEVICE
 SCHEDULE- SECTION 107.2.1 WPB. (NOT PROVIDED)
  
 8) P1.0: PROVIDE AN EQUIPMENT SCHEDULE FOR THE WATER
 HEATER INDICATING MAKE AND MODEL, ELECTRICAL DATA, GPM
 FLOW RATE ETC., AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS- SECTION 502.1 FBC P. (NOT PROVIDED)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  