Plan Review Notes
Plan Review Notes For Permit 20050837
Permit Number 20050837
Review Stop P
Sequence Number 1
Notes
Date Text
2020-06-30 14:43:021ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20050837
 6/30/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE PLUMBING FIXTURE CALCULATIONS IN ACCORDANCE
 WITH TABLE 403.3 FBC P. PROVIDE A SCHEDULE OR TABLE ON
 THE PLAN THAT INDICATES THE REQUIRED AND PROVIDED
 PLUMBING FIXTURES.
  
 2) SHEET A3.0: PROVIDE ENLARGED DIMENSIONED TOILET ROOM
 FLOOR PLANS AND DETAILS SHOWING COMPLIANCE WITH THE
 FBC-17 ACCESSIBILITY.
 A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS-
 SECTION 604.3.
 B) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORIES-
 SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS
 OR PARTITIONS- SECTION 604.2.
  
 3) A3.0- PROVIDE THESE CORRECTIONS:
 A) THE HEIGHT OF THE WATER CLOSET SEAT SHALL BE 17-19"
 MEASURED FROM THE FINISHED FLOOR TO THE TOP OF THE
 SEAT- SECTION 604.4 FBC ACC. THE DRAWING SHOWS THE
 DIMENSION AT THE BOTTOM OF THE SEAT.
 B) SHOW THE KNEE AND TOE CLEARANCES FOR THE LAVATORIES-
 SECTION 306.
 D) THE HEIGHT OF THE GRAB BARS SHALL BE 33? MINIMUM TO
 36? MAXIMUM ABOVE THE FINISHED FLOOR- SECTION 604.5 FBC
 ACC. THE DRAWING SHOWS THE DIMENSIONS AT THE CENTER OF
 THE BAR.
  
 4) A1.0 & A3.0: REFER TO SECTION 211.1.2 FBC ACC, AND
 TABLE 404.3 FBC P. NO FEWER THAN TWO DRINKING FOUNTAINS
 SHALL BE PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH SECTIONS 602.1- 602.6, AND ONE SHALL COMPLY WITH
 602.7. SECTION 602.7 REQUIRES THAT SPOUT OUTLETS FOR
 STANDING PERSONS SHALL BE 38 INCHES MINIMUM AND 43
 INCHES MAXIMUM FROM THE FINISHED FLOOR. PLEASE PROVIDE:
 A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC.
 B) KNEE AND TOE CLEARANCES- SECTION 306.
 C) SPOUT HEIGHT AND SPOUT LOCATION- SECTION 602.4 AND
 602.5.
 D) MANEUVERING CLEARANCES AT THE DOORWAYS BY THE
 DRINKING FOUNTAINS- FIGURE 404.2.4.1.
 E) COMPLIANCE WITH PROTRUDING OBJECTS- SECTION 307.2
  
 5) A1.0 & A3.0: THE NEW BREAKROOM SINK SHALL BE
 INSTALLED IN COMPLIANCE WITH SECTION 606 FBC ACC.
 PROVIDE DRAWINGS AND DETAILS.
  
 6) P1.0: TEMPERED WATER IS REQUIRED AT THE LAVATORIES-
 SECTION 416.5 FBC P. PLEASE INDICATE HOW THIS
 REQUIREMENT WILL BE MET. PLEASE NOTE THAT TEMPERATURE
 LIMITING DEVICES SHALL CONFORM TO ASSE 1070- SECTION
 607.1.2 FBC P.
  
 7) SHEET P1.0: PROVIDE A PLUMBING FIXTURE AND DEVICE
 SCHEDULE- SECTION 107.2.1 WPB.
  
 8) P1.0: PROVIDE AN EQUIPMENT SCHEDULE FOR THE WATER
 HEATER INDICATING MAKE AND MODEL, ELECTRICAL DATA, GPM
 FLOW RATE ETC., AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS- SECTION 502.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  