Plan Review Notes
Plan Review Notes For Permit 20050837
Permit Number 20050837
Review Stop M
Sequence Number 1
Notes
Date Text
2020-06-23 12:05:571ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20050837
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE TYPE OF BUSINESS THAT IS TO BE
 LEASING THIS TENANT SPACE. THE LIFE SAFETY PLANS
 INDICATE TREATMENT ROOMS. WHAT IS THE INTENDED USE OF
 THESE ROOMS? ARE THERE HAZARDOUS MATERIALS BEING STORED
 IN THIS TENANT SPACE? IF SO, PLEASE PROVIDE INFORMATION
 ON EACH INCLUDING QUANTITIES. FBC FS 107.2.1
  
 2) PLEASE PROVIDE SPECS FOR THE NEW RTU. FBC FS 107.2.1
  
 3) PLEASE PROVIDE CALCULATIONS FOR THE HEATING AND
 COOLING LOADS THAT NOTE 6 IS REFERENCING. FBC EC C403.2
  
 4) AT ANY TIME IS THE CUSTOMER INCAPACITATED DURING
 THEIR VISIT TO THIS TENANT? FBC FS 107.2.1
  
 5) PLEASE SEE BUILDING REVIEWERS? COMMENTS ON THE NEW
 RTU FOR WIND DESIGN AND ROOF ATTACHMENT. FBC FS 107.2.1
  
  
 6) PLEASE IDENTIFY ON THE M SHEET THE LOCATION OF EF-1.
 FBC FS 107.2.1
  
 7) PLEASE EXPLAIN THE EXHAUST SYSTEM IN THE TREATMENT
 ROOMS AND JANITOR?S CLOSET. FBC FS 107.2.1
  
 8) PLEASE LABEL THE SIZE OF THE MAIN EXHAUST DUCT LINE.
 FBC FS 107.2.1
  
 9) PLEASE PROVIDE A SCHEDULE IDENTIFYING WHAT THE
 LETTERS ON THE DRAWING REPRESENT (FOR EXAMPLE LETTERS N
 AND J). FBC FS 107.2.1
  
 10) PLEASE PROVIDE CFM?S AT EACH SUPPLY AND RETURN
 REGISTER. FBC FS 107.2.1
  
 11) PLEASE SHOW HOW THE AIR WILL BE RETURNED TO THE RTU
 FROM THE RECEPTION AREA. FBC FS 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  