| 2020-06-24 16:11:56 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | THIS IS A PATIENT CARE AREA AND SHALL BE WIRED AS SUCH. | | | "PATIENT CARE SPACE". SPACE WITHIN A HEALTH CARE | | | FACILITY WHEREIN PATIENTS ARE INT NDED TO BE EXAMINED | | | OR TREATED. | | | | | | INFORMATIONAL NOTE NO. 3: GENERAL CARE SPACE INCLUDES | | | AREAS SUCH AS PATIENT BEDROOMS, EXAMINING ROOMS, | | | TREATMENT ROOMS, CLINICS, AND SIMILAR AREAS WHERE THE | | | PATIENT MAY COME INTO CONTACT WITH ELECTROMEDICAL | | | DEVICES OR ORDINARY APPLIANCES SUCH AS A NURSE CALL | | | SYSTEM, ELECTRIC BEDS, EXAMINING LAMPS, TELEPHONES, AND | | | ENTERTAINMENT DEVICES. | | | | | | NEED A RISER DIAGRAM 215.5 | | | | | | LOAD CALCULATION FOR ALL LOADS IN THE PANEL. | | | | | | CONDUIT IN GROUND NEED TO BE METAL IF IN THE PATIENT | | | CARE AREA PVC IS NOT ALLOWED. 517.13.(A AND B). |
|