2020-06-24 16:11:56CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 THIS IS A PATIENT CARE AREA AND SHALL BE WIRED AS SUCH.
 "PATIENT CARE SPACE". SPACE WITHIN A HEALTH CARE
 FACILITY WHEREIN PATIENTS ARE INT NDED TO BE EXAMINED
 OR TREATED.
  
 INFORMATIONAL NOTE NO. 3: GENERAL CARE SPACE INCLUDES
 AREAS SUCH AS PATIENT BEDROOMS, EXAMINING ROOMS,
 TREATMENT ROOMS, CLINICS, AND SIMILAR AREAS WHERE THE
 PATIENT MAY COME INTO CONTACT WITH ELECTROMEDICAL
 DEVICES OR ORDINARY APPLIANCES SUCH AS A NURSE CALL
 SYSTEM, ELECTRIC BEDS, EXAMINING LAMPS, TELEPHONES, AND
 ENTERTAINMENT DEVICES.
  
 NEED A RISER DIAGRAM 215.5
  
 LOAD CALCULATION FOR ALL LOADS IN THE PANEL.
  
 CONDUIT IN GROUND NEED TO BE METAL IF IN THE PATIENT
 CARE AREA PVC IS NOT ALLOWED. 517.13.(A AND B).