| 2020-08-24 17:40:26 | RESIDENTIAL (R3) SECOND BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- PLANS SUBMITTED NOW NEED TO HAVE THE NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN AS |
| | REQUIRED BY-SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- OK. |
| | |
| | 3- PROVIDE COMPLETE FRAMING DETAIL/SPECIFICATIONS FOR |
| | THE DOUBLE DOOR. SPECIFY ALL FRAMING MEMBERS AND ALL |
| | CONNECTORS. SEC. R301.2.1 FBC-RESIDENTIAL AND SEC. |
| | 107.3.5.3 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | NO DETAIL WAS PROVIDED. NOTE: THIS DETAIL IS IMPORTANT |
| | BECAUSE THE DOUBLE DOORS ARE GOING TO BE RESTING ON |
| | THIS FRAME IN ORDER TO RESIST THE WIND LOADS. |
| | COORDINATE WITH COMMENT #6 BELOW REGARDING THE DOORS |
| | DETAILS. |
| | |
| | 4- WALL SECTION ON SHEET 2.0: |
| | A) OK |
| | |
| | B) CONNECTOR TP6X SPECIFIED TO CONNECT THE 2X4 STUDS AT |
| | TOP AND BOTTOM IS NOT CLEAR. PROVIDE CLEAR |
| | SPECIFICATIONS OF THE STRUCTURAL CONNECTOR. SPECIFY |
| | MANUFACTURER AND SPECIFIC PUBLISHED CONNECTOR. SEC. |
| | R301.2.1 FBC-RESIDENTIAL AND SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | RESPONSE: |
| | CONNECTOR WAS REMOVED. NOW THERE ARE NO SPECIFICATIONS |
| | FOR THE ATTACHMENT OF THE STUDS AT TOP AND BOTTOM. |
| | PROVIDE INFORMATION. |
| | |
| | C) OK. |
| | |
| | 5- OK |
| | |
| | 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | A) DOUBLE DOORS AS SHOWN ON PLANS. |
| | |
| | RESPONSE: |
| | (PLYWOOD DOORS OK PER ROBERT BROWN. E-MAIL DATED |
| | 06/23/2020 IF COMPLETE INFORMATION IS PROVIDED). |
| | DOOR DETAIL ON SHEET 2.0 WAS REVIEWED WITH ROBERT BROWN |
| | AND IS MISSING THE FOLLOWING INFORMATION (SEC. 107.2.1 |
| | CITY AMENDMENTS): |
| | (A) NEED TO SPECIFY TYPE OF PLYWOOD TO BE USED TO AVOID |
| | DECAY WHEN EXPOSED TO THE WEATHER. |
| | (B) NEED TO PROVIDE DETAILS SHOWING HOW ARE THE PLYWOOD |
| | EDGES PROTECTED TO AVOID DELAMINATING AND DECAYING. |
| | SEC. R317.1 FBC-RESIDENTIAL. |
| | (C) NEED TO SPECIFY DOORS LOCKING AND LATCHING |
| | HARDWARE. |
| | |
| | |
| | B) OK |
| | |
| | 7-OK |
| | |
| | 8- OK. |
| | |