| 2020-06-11 12:14:43 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- PLANS SUBMITTED HAVE A PRINT OF THE ARCHITECT'S |
| | DIGITAL SIGNATURE. NEED ORIGINAL SIGNATURE. PROVIDE |
| | PLANS WITH ORIGINAL SEAL AND SIGNATURE OR ARCHITECT TO |
| | SUBMIT PLANS ELECTRONICALLY WITH DIGITAL SIGNATURE AS |
| | REQUIRED BY 61G1-16.005 FAC. |
| | |
| | ARCHITECTS |
| | 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND |
| | SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 2- PROVIDE ROOF FRAMING PLAN. SPECIFY ALL ROOFING |
| | MEMBERS SIZES, SPACING AND CONNECTORS. SEC. R301.2.1 |
| | FBC-RESIDENTIAL AND SEC. 107.3.5.3 CITY AMENDMENTS. |
| | |
| | 3- PROVIDE COMPLETE FRAMING DETAIL/SPECIFICATIONS FOR |
| | THE DOUBLE DOOR. SPECIFY ALL FRAMING MEMBERS AND ALL |
| | CONNECTORS. SEC. R301.2.1 FBC-RESIDENTIAL AND SEC. |
| | 107.3.5.3 CITY AMENDMENTS. |
| | |
| | 4- WALL SECTION ON SHEET 2.0: |
| | A)PROVIDE DETAIL/SPECS FOR THE DRIP EDGE AS REQUIRED BY |
| | SEC. R905.2.8.5 FBC-RESIDENTIAL. |
| | |
| | B) CONNECTOR TP6X SPECIFIED TO CONNECT THE 2X4 STUDS AT |
| | TOP AND BOTTOM IS NOT CLEAR. PROVIDE CLEAR |
| | SPECIFICATIONS OF THE STRUCTURAL CONNECTOR. SPECIFY |
| | MANUFACTURER AND SPECIFIC PUBLISHED CONNECTOR. SEC. |
| | R301.2.1 FBC-RESIDENTIAL AND SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | C)SPECIFY HOW MUCH EMBEDMENT IS REQUIRED FOR THE 3/8" |
| | ZINC PLATED WEDGE ANCHORS SPECIFIED IN THE WALL SECTION |
| | TO FASTEN THE 2X4 BOTTOM PLATE. |
| | SEC. R301.2.1 FBC-RESIDENTIAL AND SEC. 107.3.5.3 CITY |
| | AMENDMENTS. |
| | |
| | 5- PLANS SPECIFY 3:12 ROOF PITCH. NEED TO SPECIFY TWO |
| | LAYERS OF UNDERLAYMENT AS REQUIRED BY SEC. R905.2.2 |
| | FBC-RESIDENTIAL. |
| | |
| | 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | A) DOUBLE DOORS AS SHOWN ON PLANS. (OK PER ROBERT |
| | BROWN. E-MAIL DATED 06/23/2020) |
| | |
| | B) ROOF SHINGLES. |
| | |
| | 7-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 8- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW. |
| | VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S |
| | OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS |
| | REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE |
| | VALUATION TO INCLUDE ALL COSTS OR PROVIDE COPY OF |
| | SIGNED CONTRACTS INCLUDING DESIGN PROFESSIONAL FEES. |
| | |