| Plan Review Notes For Permit 20050820 |
| Permit Number |
20050820 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-05-29 09:26:44 | ROOFING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED ON THE | | | PROVIDED PRODUCT APPROVAL - SYSTEM CIRCLED MAY REQUIRE | | | ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN | | | ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH | | | REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE | | | PRODUCT APPROVAL - SEE NOTE NUMBER 7 ON THE PRODUCT | | | APPROVAL. SIGNED AND SEALED DRAWINGS OR DOCUMENTS WILL | | | NEED TO BE DIGITALLY SIGNED AND SEALED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. DRAWING S-6 ON PERMIT 18111203 | | | SHOWS P1 = (-55.8) P2 = (-97.2) P3 = (-97.2) | | | | | | FYI = ENGINEER CANNOT SELF-CERTIFY THE DIGITAL | | | SIGNATURE | | | 668.003(2) AND (3), F.S. | | | (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL | | | SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING | | | PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL HAVE | | | THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION | | | AUTHORITY. | | | |
|