| Plan Review Notes For Permit 20050813 |
| Permit Number |
20050813 |
|
| Review Stop |
PW |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-07-16 11:28:20 | 1- PLEASE UPDATE THE ENCLOSURE ORIENTATIONS TO ALLOW | | | FOR SAFE ACCESSIBILITY AND SERVICE BY OUR FRONT LOADER | | | TRUCKS. IT IS RECOMMENDED TO CHANGE THE ORIENTATION TO | | | 45 DEG. (NORTH EAST DIRECTION) TO THE FLOW OF INCOMMING | | | TRAFFIC COMING FROM THE SOUTH SIDE OF THE BUILDINGS. | | | 2- PLEASE UPDATE THE ENCLOSURE DETAIL, TO REFLECT | | | REQUIREMENTS SPECIFIED IN OUR ENSLOSURE SPEC. GC-7, | | | SUCH AS: | | | A- 5 FT HEIGHT | | | B- ALL HARDWARE SHALL BE HOT DIPPED GALVENIZED | | | C- CONCRETE PAD AS SPECIFIED ON THE GC-7 | | | D - GATE OPENING 13 FT MIN. | | | E- ETC. | | | | | | MATT HEJAZI | | | [email protected] | | | 561-822-2045 |
|