| Notes |
| Date |
Text |
| 2020-06-01 09:53:47 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | | | | 1) THE SUBMITTED PALN DOES NOT INDICATE SMOKE | | | ALARMS(SA) OUTSIDE OF THE SLEEPING AREAS OF THE TWO | | | BEDROOMS. | | | | | | PER NFPA 101, CH 32 NEW RESIDENTIAL BOARD AND CARE | | | OCCUPANCIES | | | | | | 32.3.3.4.7 SMOKE ALARMS. APPROVED SMOKE ALARMS SHALL BE | | | INSTALLED IN ACCORDANCE WITH 9.6.2.10 INSIDE EVERY | | | SLEEPING ROOM, | | | OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY | | | OF THE | | | BEDROOMS, AND ON ALL LEVELS WITHIN A RESIDENT UNIT. | | | | | | PLEASE REVIEW AND CORRECT OF JUSTIFY WITH SPECIFIC | | | INFORMATION AND CODE REFERENCES. | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|