| 2020-05-29 08:55:30 | 1) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU |
| | LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE |
| | TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. |
| | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR |
| | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. |
| | 2) EXISTING GAS PLANS ON FILE WITH THE CITY SHOW THE |
| | LONGEST RUN AS 140 FEET TO THE MOST REMOTE OUTLET BUT |
| | THE SUBMITTED GAS PLAN SHOWS ONLY ONE RUN AT 45 FEET. |
| | CLARIFY. |
| | 3) SHOW THE TYPE OF PIPE AND THE SIZE OF THE PIPE AT |
| | THE OUTLET (CONSUMER SIDE) OF THE GAS METER. THIS LINE |
| | SHALL BE SIZED FOR THE TOTAL BTU LOAD ON THE SYSYTEM |
| | AND THE TYPE OF PIPE. |
| | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GENERATOR. FBC-FUEL GAS SEC.305.1. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |