| Plan Review Notes For Permit 20050786 |
| Permit Number |
20050786 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-05-28 10:09:13 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) INDICATE THE SYSTEM NUMBER AND THE MAXIMUM DESIGN | | | PRESSURE FROM THE TABLES IN THE MODIFIED BITUMEN | | | ROOFING PRODUCT APPROVAL. IF THE MAXIMUM DESIGN | | | PRESSURE IS LESS THAN REQUIRED FOR THE PERIMETER AND | | | CORNER AREAS IN EXPOSURE C IN A 170 MPH WINDSPEED | | | (-95.7PSF FOR 15' MRH), THEN YOU WILL HAVE TO SUBMIT | | | SIGNED AND SEALED ENHANCED FASTENING CALCULATIONS. FBC | | | 107.2.1 | | | | | | 2) INDICATE THE MINIMUM ATTACHMENT RESISTANCE FOR THE | | | ROOF TILE BY MARKING THE APPLICABLE ITEMS IN TABLE 5 OR | | | 6 OF THE PRODUCT APPROVAL. FBC 107.2.1 | | | | | | 3) MARK THE APPLICABLE TILE PROFILE AND ADHESIVE | | | PLACEMENT DETAIL ON THE TILE ADHESIVE PRODUCT APPROVAL. | | | FBC 107.2.1 |
|