| 2021-03-09 10:01:36 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) THE RESPONSE FROM THE FIRE SPRINKLER CONTRACTOR | | | STATING A CODE SECTION FROM NFPA 13 MAY NOT | | | SPECIFICALLY APPLY IN THIS INSTANCE. | | | | | | THE CODE SECTION QUOTED 8.15.3.2.3.1 FALLS UNDER | | | 8.15.3.2 NONCOMBUSTIBLULE CONSTRUCTION. | | | | | | THE PROPOSED STAIRS ARE WOOD/COMBUSTIBULE. | | | | | | A MORE SPECIFIC CODE INDICATES THAT FIRE SPRINKLESR | | | SHALL BE INSTALLED UNDER COMBUSTIBLE STAIRS. | | | | | | PER NFPA 13 | | | | | | 8.15.3 STAIRWAYS. | | | | | | 8.15.3.1 COMBUSTIBLE CONSTRUCTION. SPRINKLERS SHALL BE | | | INSTALLED | | | BENEATH ALL STAIRWAYS OF COMBUSTIBLE CONSTRUCTION. | | | 8.15.3.1.1 SPRINKLERS SHALL BE INSTALLED AT THE TOP OF | | | COMBUSTIBLE | | | STAIR SHAFTS. | | | 8.15.3.1.2* SPRINKLERS SHALL BE INSTALLED UNDER THE | | | LANDINGS AT | | | EACH FLOOR LEVEL. | | | 8.15.3.1.3 SPRINKLERS SHALL BE INSTALLED BENEATH THE | | | LOWEST INTERMEDIATE | | | LANDING. | | | | | | | | | IN AN EFFORT TO MOVE THIS PROJECT FORWARD, THIS PERMIT | | | WILL BE PASSED WITH PROVISO TO ADDRESS THE STIAIR FIRE | | | PROTECTION OF THE SHOP DRAWINGS. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|