| 2021-02-22 13:54:07 | |
| | |
| | FAILED BY FIRE WITH COMMENTS: |
| | |
| | |
| | 1) THE FP PLANS DO NOT INDICATE FIRE SPRINKLER |
| | PROTECTION UNDER THE INTERIOR EXIT STAIRS. |
| | |
| | PER NFPA 13, |
| | |
| | 8.15.3 STAIRWAYS. |
| | 8.15.3.1 COMBUSTIBLE CONSTRUCTION. SPRINKLERS SHALL BE |
| | INSTALLED |
| | BENEATH ALL STAIRWAYS OF COMBUSTIBLE CONSTRUCTION. |
| | 8.15.3.1.1 SPRINKLERS SHALL BE INSTALLED AT THE TOP OF |
| | COMBUSTIBLE |
| | STAIR SHAFTS. |
| | 8.15.3.1.2* SPRINKLERS SHALL BE INSTALLED UNDER THE |
| | LANDINGS AT |
| | EACH FLOOR LEVEL. |
| | 8.15.3.1.3 SPRINKLERS SHALL BE INSTALLED BENEATH THE |
| | LOWEST INTERMEDIATE |
| | LANDING. |
| | |
| | FOR CLARIFICATION PRUPOSES, PLEASE INCLUDE A DETAILED |
| | REVIEW OF THE PROPOSED CONSTRUCTION AND THE PROTECTION |
| | OF THE STAIRWAYS PER THE CODE. |
| | |
| | |
| | |
| | 2) WPB FEB 2021 SHEET A4 - THERE DOES NOT APPEAR TO BE |
| | A CLEAR INDICATION OF THE EXTERIOR EXIT STAIRWAY |
| | CONSTRUCTION MATERIAL. THERE IS AN INDICATION OF AN |
| | ALUMINUM RAILING, BUT NO THE STAIRWAY. |
| | |
| | PER NFPA 101 |
| | |
| | 30.2.2.3 STAIRS. |
| | 30.2.2.3.1 STAIRS COMPLYING WITH 7.2.2 SHALL BE |
| | PERMITTED. |
| | |
| | |
| | 7.2.2.5 SPECIAL PROVISIONS FOR EXTERIOR STAIRS. |
| | |
| | 7.2.2.5.1 LANDINGS. LANDINGS TO WHICH EGRESS DOORS LEAD |
| | SHALL |
| | BE APPROXIMATELY LEVEL [WITHIN 1 CM (3?8 IN.)] WITH THE |
| | ADJOINING |
| | DECK. |
| | 7.2.2.5.2 EXTERIOR STAIRS SHALL BE PERMITTED TO BE USED |
| | AS A |
| | COMPONENT OF EGRESS WHERE THERE IS AN OBVIOUS ROUTE OR |
| | EGRESS |
| | DIRECTION SIGNAGE LEADING TO AN AREA OF SAFE REFUGE OR |
| | AN EMBARKATION |
| | AREA. |
| | 7.2.2.5.3 EXTERIOR STAIRS SHALL BE CONSTRUCTED OF |
| | NONCOMBUSTIBLE |
| | MATERIAL. |
| | |
| | 7.2.2.5.5 EXTERIOR STAIRS SHALL COMPLY WITH THE |
| | REQUIREMENTS |
| | OF TABLE 7.2.2.5.5 AND SUBSEQUENT SECTIONS. |
| | |
| | FOR CLARIFICATION PURPOSES PLEASE REVIEW AND INCLUDE A |
| | DETAILED REVIEW OF THE PROPOSED CONSTRUCTION OR PROVIDE |
| | THE SHEET LOCATION CONTAINING THE REQUIRED INFORMATION. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |