| 2020-11-23 17:26:40 | 11/23/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SIGNED AND SEALED DRAWINGS NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - |
| | IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL |
| | SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE |
| | ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN |
| | REVIEW REQUEST FORM" EXPLAINING THE REASON FOR |
| | SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW |
| | REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND |
| | ASKING FOR THE FORM. |
| | |
| | 2. PLEASE PROVIDE SPECIFICATIONS FOR TANKLESS ELECTRIC |
| | WATER HEATER PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. THERE TWO TUBS AND ONE SHOWER THAT SHOW AIR |
| | ADMITANCE VALVES BEHIND THEM, THEY NEED TO HAVE AN |
| | ACCESS PANEL OR YOU CAN RE-VENT THEM PLEASE SHOW ON |
| | ISOMETRIC OR MAKE NOTES ON PLANS FOR ACCESSIBLE |
| | LOCATION PER THE 2017 FBC SEC. 918.5 ACCESS AND |
| | VENTILATION. |
| | |
| | 4. ON ISOMETRIC P-4 AND P-2, UNIT 4 HAS THE KITCHEN IN |
| | A BATHROOM GROUP WET VENT AND IT MUST RUN DOWNSTREAM OF |
| | THE GROUP PER THE 2017 FBC SEC. 912.1 HORIZONTAL WET |
| | VENTS PERMITTED. |
| | |
| | 5. ON ISOMETRIC P-4 RISER D 2?, UNIT 2 BATH AND |
| | KITCHEN, AND RISER 3? HAVE ENTRY TO THE BUILDING WITH |
| | THE CLEANOUT AND MUST BE VENTED THROUGH ROOF AND MUST |
| | HAVE A MINIMUM OF ONE STACK VENT OR VENT STACK EXTENDED |
| | TO THE OUTDOORS TO THE OPEN AIR PER THE FBC SEC. P |
| | 918.7. SHOW COMPLIANCE WITH THE PLANS. |
| | |
| | 6. ON ISOMETRIC P-4 CLEANOUT NOT SHOWN ON BATH AND |
| | KITCHEN WITHIN 10 FT OF ENTERING BUILDING PER THE PER |
| | THE 2017 FBC 708.1.3 BUILDING DRAIN AND BUILDING SEWER |
| | JUNCTION. |
| | |
| | 7. SHEET P-1 UNIT 1 HAS A STACKABLE WASHER AND DRYER |
| | AND ACCESS TO SHUT OFF VALVE MUST BE REACHABLE WITHOUT |
| | MOVING THE UNIT PLEASE MAKE NOT ON PLANS PER THE 2017 |
| | FBC SEC. P 606.3. ACCESSIBLE SIGNIFIES ACCESS THAT |
| | REQUIRES THE REMOVAL OF AN ACCESS PANEL OR SIMILAR |
| | REMOVABLE OBSTRUCTION. |
| | |
| | 8. SHEET P-1 UNIT 1 AND OTHERS DO NOT HAVE A WASHING |
| | MACHINE HOOK ARE THEY IN A DIFFERENT LOCATION, PLEASE |
| | CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |