| Date |
Text |
| 2020-11-23 11:27:04 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20050783 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE A SCOPE OF WORK FOR THE MECHANICAL |
| | SYSTEMS FOR THIS PROJECT. THE DRAWINGS INDICATE TOTALLY |
| | NEW SYSTEMS. IF ALL SYSTEMS ARE NEW PLEASE PROVIDE THE |
| | LIKE FOR LIKE DOCUMENTATION FOR EACH UNIT REPLACED. |
| | CITY RECORDS INDICATE THERE ARE NO RECORDS THAT A HVAC |
| | SYSTEM HAS BEEN INSTALLED IN THESE APARTMENTS. PLEASE |
| | PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS. |
| | THE MECHANICAL PERMIT MUST ALSO INCLUDE THE VALUE OF |
| | THE PROJECT. FBC 107.2 FBC EC FBC EC C403.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |